HW14 telecom site environment & power remote monitoring
USD $1 - $500 /Set
Min.Order:1 Set
Hangzhou Xinjian Electronic Co., Ltd.
It starts DC fans first to save energy, and controls them based on indoor temperature and humidity, outdoor temperature. Then controller starts air-conditioner if temperature is higher. Control logic is smart, simple and stable.
Function: | |
Set | Contains 4 buttons to set |
Display | 5 pcs of 0.56’’ LEDs and 4 pcs of LED lights |
Control | Control DC fans and 2 air-conditioner based on temperature and humidity |
Alarm | Output a alarm signal (dry node) |
Power detection | AC power and battery voltage, if AC power off or voltage of battery is lower than DC 46V output alarm signal |
Work state detection | Detect the frequency of fan to judge if DC fan has fault, and use current sensor to detect if air-conditioner has fault |
Manual test | Start DC fans or air-conditioner by manual |
Initialize parameter | Initialize running parameter by a combination key |
Communication | Supply RS485 communication interface, and supply software for free |
Performance Indices: | |
Type | XJW-HW14 |
Installation | Wall-mounted |
Temperature detect range | -40°C ~ 70°C |
Humidity detect range | 0% ~ 99% |
Size | 300x400x150 |
Sensor: | |||
Type | Name | Number | Note |
WD | Temperature sensor | 1 | Accessories, fixed outside |
WS2 | Hygrothermograph sensor | 1 | Accessories, fixed inside |
SS-168P | Smog sensor | 1 | Accessories, fixed inside |
TT | Immersion sensor probe | 1 | Accessories, put it on the floor |
DD5 | Power off sensor | 1 | Fixed in the box |
IA5 | Current sensor | 1-2 | Fixed in the box |
Alarm code | Meaning |
E01 | High room temperature |
E03 | Smog fire alarm |
E04 | AC power off alarm |
E08 | Temperature sensor has fault |
E09 | Low voltage of battery |
E11 | Air-conditioner I has fault |
E12 | Air-conditioner II has fault |
E21 | DC fan has fault |