Overview
Outdoor HV solation vacuum load switch from my company and Xi’an High Voltage Apparatus Research joint research and development by the company’s first production of a new generation of high-voltage electrical products, through rigorous testing and long-term test pattern running evaluation, the technical performance indicators and IEC standards all reached GB3840 for Rated voltage 12KV, Rated Current 630A, three-phase AC 50Hz supply point network.
Main technical parameters
Serial number | Project | Unit | Parameter | |
1 | Rated voltage | KV | 12 | |
2 | Rated frequency | Hz | 50 | |
3 | Rated Current | A | 630 | |
4 | Rated active load breaking current | A | 630 | |
5 | Rated closed-Loop breaking current | A | 630 | |
6 | 5%Rated active load breaking current | A | 31.5 | |
7 | Rated cable charging breaking current | A | 10 | |
8 | Rated no-load transformer breaking capacity | 1600 | ||
9 | Rated breaking current of capacitor | A | 100 | |
10 | 1min power frequency withstand voltage :vacuum Fracture,white, relative to /solation Fracture | KV | 42/48 | |
11 | Lightning impulse withstand mortgage:white, relative to /solation Fracture | KV | ||
12 | Rated short time withstand current (heat stable) | KA | 20 | |
13 | Rated short circuit duration | S | 4 | |
14 | Rated peak withstand current (dynamic stability) | KA | 50 | |
15 | Rated short circuit making current | KA | 50 | |
16 | Mechanical life | Times | 10000 | |
17 | vacuum interrupter contacts to allow wear | mm | 1 | |
18 | Manual torque | N.m | ≤200 | |
19 | Adjustment of load switch vacuum Interrupter assembly | Contact opening distance | mm | 5±1 |
Average gate speed | m/s | 1.1±0.2 | ||
Different points of three-phase gate | ms | < 5 | ||
Different points of three-phase gate | ms | < 2 | ||
Charged and relative distance between | mm | > 200 | ||
secondary circuit resistance | υΩ | ≥400 |