GW8 GW13 High Voltage Outdoor Neutral Point Disconnector Switch
USD $13 - $250 /Set
Min.Order:1 Set
Yueqing Hossin Electrical Co., Ltd.
GW8 GW13 High Voltage Outdoor Neutral Point Disconnector Switch
Name | units | (H)GW8-40.5 | (H)GW8-72.5 | (H)GW8-126 |
Rated voltage | KV | 40.5 | 72.5 | 126 |
Rated current | A | 4,006,301,250 | ||
4SRated short time withstand current(Eff.) | KA | 8,20,31.5 | ||
Peak withstand current(ampl.) | KA | 20,50,80 | ||
1min. power frequency withstand voltage | KV | 80 | 140 | 185 |
Rated lightning impulse withstand voltage | KV | 185 | 325 | 450 |
Mechanical life | TIME | 2000 | 2000 | 2000 |
Rated mechanical vertical ]terminal load Horizontal | N | 800 | 800 | 800 |
N | 120 | 200 | 200 | |
leakage distance | Mm/kv | 16(Ⅰ )20(Ⅱ )25(Ⅲ ) | ||
The operating torque of the manual mechanism | Nm | ≤200 | ||
weight of single pole | KG | 160 | ||
Mechanism supplied for disconnector | CS8-5 Manual operating mechanism or CJ6 horizontal type motor drive mechanism | |
Name | units | (H)GW8-40.5 | (H)GW8-72.5 | (H)GW8-126 |
Rated voltage | KV | 40.5 | 72.5 | 126 |
Rated current | A | 630 | 630 | 630 |
4SRated short time withstand current(Eff.) | KA | 8 | 20 | 20 |
Peak withstand current(ampl.) | KA | 20 | 50 | 50 |
Rated short circuit duration | S | 2 | 2 | 2 |
1min. power frequency withstand voltage | KV | 80 | 140 | 95 |
1.2/50μS lighting impulse withstand voltage | KV | 185 | 325 | 250 |
The operating torque of the manual mechanism | N.m | 150 | ||
Mechanical life | times | 2000 | 2000 | 2000 |
The Minimum insulation gap after open | Mm | ≥375 | ≥675 | ≥1050 |
Main loop resistance | μΩ | ≤180 | ≤200 | ≤250 |
Weight of single pole | kg | 120 | 125 | 150 |
Mechanism supplied for disconnector | CS17GManual mechanism or CJ6,CK7 electric mechanism | |||
|