Features
1. Adopt advanced imported catalytic combustion sensor
2. Reliable, sensitive and long performance life
3. High resistance to poison, good disturb-proof against
temperature and humidity
4. Automatic zero calibration can avoid long-term zero
drift caused by measurement error
5. Concentration signal output
6. Over-current protection, Anti-polarity protection
7. 4-20mA communication interface can use with our
CA-2100A or CA-2100F controllers
8. Scope of working voltage: DC20V~DC30V
Specifications
Detection Principle: Catalytic Combustion
Detection Method: Diffused
Applicable Gas: Combustible Gases
Working Method: Continuous Working
Detection Scope: 0~100%LEL
Respond Time: <=30S
Detection Error: <+-3%LEL
Environment Temperature: -40°C~+70°C
Relative Humidity: 30%-95%
Output Signal: Concentration Digital Signal
Working Voltage: DC20V~DC30V
Sensor Life Span: 3 Years
Transmission Distance: <=1000m
Operation Pressure: (86-106) kPa
Detector Size: 158*130*93mm
Explosion-proof Level: Exd II CT6
Connection Thread : 1/2G Inner Thread
Weight: 1kg
Communication: 4-20mA Standard Current