1Product Introduction

       Smoke sensor is a kind of alarm equipment in firefighting management and security system. It is of small size but reliable. Smoke sensor combines signal output and fire smoke sensor organically, which makes it easily installed and flexible used. Smoke sensor is suitable for less smoking, non smoking place to detect smoke ion to detect smoke accurately .When the smoke scope exceed the limitation ,the sensor will warn via sound-light alarm and output warning signal to the collector.

 

2 Product Specification

2.1 Product Installment

 

2.1.1 Smoke sensor is not suitable for the following places:

       A).The place with smoke in normal situation

       B).The place where the humidity rate is more than 95% 

       C).The place with much dust, spray and oil spray 

       D).The place with high speed wind.(more than 5 meters/s)

 

2.1.2 Connect the battery and battery buckle. Select the appropriate installing location, install the smoke sensor in the middle ceiling of the detecting space. Then use screws to fix base of detector in the chosen location, and put the smoke sensor in, rotate it and check whether it is firm.

 

 

2.2 Using Instruction

 1).On DC 12 v power supply, connect the red line to the anode, the black to the cathode. The white line is for the public terminal, the orange line is normally open, and the yellow line is normally closed.


 2).Once connected to the power, the smoke sensor begins normally monitoring with the indicator light flashing every 45 seconds.


 3).Testing: in order to ensure the normal work of the sensor, regular tests are necessary, suggesting once a month. Press the test button when testing, If the alarm indicator lights is flashing fast, and the buzzer is alarming , the smoke sensor works normally.


 4).Smoke alarm: when the concentration of smoke in the surrounding environment exceeds the alarm value, the detector alarm indicator lights will flash fast, and the buzzer alarms.


 5).Low voltage battery detection: when the battery voltage is lower than the normal working voltage, the buzzer alarm every 45 seconds. In this case, you should promptly replace the battery. Otherwise, it will affect the normal work of the smoke sensor.

 

 

 

2.3 Technical Parameters

 

Model

HM-608PC-4

2/4line

4line

Working Voltage

DC9-16V

Product Category

Four wire type connected to the Internet

Size

Φ100*55mm

Quiescent Current

≤200uA

Alarming Indicator

Flashing red LED light

Alarming Sound Pressure

≥85dB/1m

Working Temperature

-10℃~ +50℃

Relative Humidity

≤95%RH

Operation Standard

GB4715-2005; EN14604

Cover Area

       When space is 6 meters to 12 meters high, protection area of a smoke sensor is 80 square meters; Space height is less than 6 m, protection area is 60 square meters. Specific parameters should according to automatic fire alarm system design specifications BG50116-98.

 

 

 

3,Product Appearance

        

Smoke Sensor/Smoke Monitor/Environment Monitoring 

                          

                                                      Smoke Sensor/Smoke Monitor/Environment Monitoring

 

 

4,Dimension (Precision:±3mm)

 

 

Smoke Sensor/Smoke Monitor/Environment Monitoring

 

 

 

 

5,Connection

 

             Smoke Sensor/Smoke Monitor/Environment Monitoring

You May Like

Find Similar Products By Category

You May Like

View More
Chat Now Contact Now