CE certificate 10kva 10000va 220v 230v 240v tower online ups power external battery model type
Product Specifications:
HT1106S | HT1106L | HT1110S | HT1110L | |
INPUT | ||||
Cold Start | YES, default frequency=50Hz or settable | YES, default frequency=50Hz or settable | ||
Acceptable Input Voltage | 50%~125%(220VAC/230VAC/240VAC) | 50%~125%(220VAC/230VAC/240VAC) | ||
100% load@80%~125% | 100% load@80%~125% | |||
90% load@70%~80% | 90% load@70%~80% | |||
80% load@60%~70% | 80% load@60%~70% | |||
65% load@50%~60% | 65% load@50%~60% | |||
Phase | Single phase in,single phase out | Single phase in,single phase out | ||
Transfer Voltage Range | ||||
-Line low transfer | 110VAC/115VAC/120VAC | 110VAC/115VAC/120VAC | ||
-Line low recovery | 116VAC/122VAC/127VAC | 116VAC/122VAC/127VAC | ||
-Line high transfer | 275VAC/288VAC/300VAC | 275VAC/288VAC/300VAC | ||
-Line high recovery | 268VAC/279VAC/291VAC | 268VAC/279VAC/291VAC | ||
Input Power Factor | ≥0.99 | ≥0.99 | ||
Input Frequency Range | 40Hz - 70Hz | 40Hz - 70Hz | ||
Generator | Support Any Generator. | Support Any Generator. | ||
OUTPUT | ||||
Frequency adaptable | Settable | Settable | ||
Power | ||||
-Power(kVA) max | 6 | 10 | ||
-Power(kW) max | 5.4 | 9 | ||
Output Voltage | ||||
-Waveform | Pure sine wave | Pure sine wave | ||
-Nominal voltage | 220/230/240VAC | 220/230/240VAC | ||
-Voltage regulation | ± 1 % | ± 1 % | ||
-Transient response | ≤5% (50% - 100% -50%) | ≤5% (50% - 100% -50%) | ||
-Transient recovery | ≤15ms (0% - 100% -0%) | ≤15ms (0% - 100% -0%) | ||
-Voltage distortion | ≤1% THD, linear load | ≤1% THD, linear load | ||
≤ 5% THD, non-linear load | ≤5% THD, non-linear load | |||
Output Frequency | ||||
-Synchronization range | settable,±3Hz default | settable,±3Hz default | ||
-Slew rate | 0.5~5Hz/s,2 Hz/s default | 0.5~5Hz/s,2Hz/s default | ||
-Battery mode | (50±0.05) Hz | (50±0.05) Hz | ||
Transfer Time | ||||
-Line mode to battery mode | 0 | 0 | ||
-Inverter to bypass | 4ms | 0 | ||
Efficiency | ||||
-Line mode with battery full charged | 93.0% | 93.0% | ||
-ECO mode | 98.0% | 98.0% | ||
-Battery mode | 92.0% | 92.0% | ||
Noise | <48dB@<70%load,<58dB@>70%load;1m away | <48dB@<70%load,<60dB@>70%load;1m away | ||
Overload Capability (Line Mode) | 110%: Transfer to bypass after 10 mins. | 110%: Transfer to bypass after 10 mins | ||
130%: Transfer to bypass after 1 min | 130%: Transfer to bypass after 1 min | |||
150%: Transfer to bypass after 30s, shutdown after 1 min.(Line mode) | 150%: Transfer to bypass after 30s, shutdown after 1 min.(Line mode) | |||
Overload Capability (Battery Mode) | 110%: Shutdown after 10mins (Battery mode) | 110%: Shutdown after 10mins (Battery mode) | ||
125%:Shutdown after 10s(Battery mode) | 125%:Shutdown after 10s(Battery mode) | |||
>125%: Shutdown after 1s (Battery mode) | >125%: Shutdown after 1s (Battery mode) | |||
Crest Ratio | 3:1 | 3:1 | ||
BATTERY | ||||
Rating/Type | 12VDC/7Ah | Depend on the capacity of external batteries | 12VDC/9Ah | Depend on the capacity of external batteries |
Quantity | 16 | 16 | ||
DC Voltage | 192VDC | 192/240VDC | 192VDC | 192/240VDC |
Back-up Time | 4mins @80% load | Depend on the capacity of external batteries | 3.5mins @80% load | Depend on the capacity of external batteries |
Battery-Low Voltage | (176±3)VDC | (176±3)VDC | ||
Charger | ||||
-Charging voltage | (220±1%)VDC | (220±1%)VDC | ||
-Charging current (max) | 1A | 5A | 1A | 5A |
-Charging time | 7h recharge to 90% | Depend on the capacity of external batteries | 8h recharge to 90% | Depend on the capacity of external batteries |
Leakage current | <1mA | <1mA | ||
INDICATOR & ALARM | ||||
Display | LED+LCD | LED+LCD | ||
Alarm | Sounding once per second | |||
Fault | Continuous beeping | |||
INTERFACE | ||||
Smart RS232 | Standard Cable support INVT Power Monitor Software | |||
B type USB(optional) | Standard Cable support INVT Power Monitor Software | |||
EPO | Remoted EPO function for customer. Short to activate | |||
Dry Contactor(optional) | DB9 type and phoenix terminal type for selection. (6 output ports, 1 input port) UPS fault alarm, general alarm, bypass mode, UPS normal mode, battery low voltage alarm, utility failure alarm, remoted shutdown. | |||
SNMP(optional) | Power Managment from SNMP Manager and Web Browser | |||
Option | SNMP, USB, Dry Contactor(AS400),Parallel Kit, ECO Kit, External Battery Cable(standard model), Maintenance Bypass, Maintenance Bypass | |||
Reserved function | Can be designed as deffirent function according to customer's application | |||
MECHANICAL | ||||
W*D*H (mm) | 250*562*650 | 250*504*480 | 250*562*650 | 250*504*480 |
Net Weight (KG) | 57 | 18 | 65 | 20 |
Color | Black | Black |
Product Images:
Our Factory:
Our Exhibitions:
Product Certifications:
Shipping:
FAQ:
Product Quality: We are a public company(stock code: 002334) and owned 800-900 engineers for the control of product quality.
Delivery Time: Usually 15-20days, it depends to your specific order information.
Package: We have professional wooden package for large machine.