Product Details

AC dummy load bank 100kw

Place of Origin Shaanxi, China
Brand Name AITELONG
Model Number SAT-ACO
Power Electronic
Usage Auto Testing Machine

Product Features

 

Product Description

 

SAT-ACO380/10 AC load is ac dummy load bank 100kw   

 

Functions & Features

 

-Test discharge three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time, energies of generators and UPS.

-Set/adjust discharging power according to performance parameters and detection requirements

-Set discharging time, timing to automatic shut-off load, discharge off and alarm operator

-Set over/under voltage protection threshold value, it can shut off load, terminate discharging and alarm user automatically.

-Large LCD screen, friendly interface. English menu and easy operation.

-Parallel operation function to carry out multi sets load operation by RS 485 communication

-Built-in storage function, save 30 groups of test data, which can be inquired, deleted and put into SD card.

-Start/stop discharging control by Serial port, and detect data real time operation etc; The storage data can be uploaded to PC by serial port or SD card, and the upper computer’s software can analyze data and pattern and print report etc.

-Overheating and over current protection function, it can turn off load, terminate discharging and alarm automatically when over temperature and over current.

-Set at most 5 groups power, load process automatically according to the setting power and operation time after being turned on. 

Technical Parameters

 

Mode

ACO 380/02

ACO 380/04

ACO 380/10

Working environment

Working Temperature: (-20~55)℃       

Storage Temperature: (-45~75)℃

Relative humidity: 90%(40±2℃)

Atmospheric pressure: (70~106)KPa

Working power supply

Single-phase AC220V±10, 50Hz

Load voltage

Three-phase AC380V, Single-phase AC220V

Operating power

Stand-alone: Max 20KW (Three-phase 380V)

Max 6KW (Singly-phase 220V)

Stand-alone: Max 40KW (Three-phase 380V)

Max 13KW (Singly-phase 220V)

Stand-alone: Max 100KW (Three-phase 380V)

Max 30KW (Singly-phase 220V)

Cooling mode

FCT(Fan control Temperature)

Communication Mode

RS232, RS485 and SD card

Display mode

8 inch TFT

Voltage measurement range

AC 0~450V, Display Resolution: 0.1V, Precision: ±0.5%

Current measurement range

AC 0~100A, Display Resolution: 0.1A, Precision: ±0.5%

AC 0~150A, Display Resolution: 0.1A, Precision: ±0.5%

AC 0~300A, Display Resolution: 0.1A, Precision: ±0.5%

Frequency measurement range

40~60 Hz, Display Resolution: 0.01Hz, Precision: ±0.2%

Power measurement range

0~20 KVA, Display Resolution: 0.1KVA, Precision: ±1%

0~40 KVA, Display Resolution: 0.1KVA, Precision: ±1%

0~100 KVA, Display Resolution: 0.1KVA, Precision: ±1%

Power factor measurement range

0.001~1.000, Display Resolution: 0.001, Precision: ±0.5%

Discharging Time

(0~19 hours and 59 minutes) adjustable continuously

Quantity of Parallel operation

1~99 sets

Recording Period

6~999 Seconds

Temperature measurement range

-20~100℃,Display resolution: 1℃, precision:±1℃

Insulating strength

Input≥AC1500V

Output≥AC500V

MTTF

≥50000h

Dimensions(mm)

420×500×750mm

680×600×900mm

680×600×900mm

Weight

30kg

50kg

70kg

 

 

Company Information

AC dummy load bank 100kw 

 

Production Line

AC dummy load bank 100kw 

 

You May Like

Find Similar Products By Category

You May Like

View More