Acrel ARCM200L-T16 multi channel electrical fire monitoring detector 16 channel temperature controller

Usage Current Measurement
Accuracy 1.0

Product Features

Product Description

ARCM200L series multi-circuit type electrical fire monitoring detector (hereinafter referred to as the detector), is  designed for 0.4 kV below TT, TN system design, through the monitoring and management of distribution of residual current circuit, the conductor temperature, over current, over voltage fire danger parameters, to prevent the happening of the electrical fire, and realizes  the real-time monitoring of various power parameters, and provide data for energy consumption management.

The product adopts advanced microcontroller technology, is of high integration, small size, easy installation. It integrates it with intelligentization, digitalization, network, is an ideal choice for building electrical fire prevention monitoring, insulation aging prediction of the system.

The products meet the standard requirements of GB14287.2-2014 electrical fire monitoring system part 2: residual current electrical fire monitoring detector and GB4287.3-2014 electrical fire monitoring system part 3: temperature measuring electrical fire monitoring detector.

2 Product model

Technical parameters

 Sheet 1

Technical parameters 

ARCM200L

Input

 

Network

 

Three phase TT,TNS,TN-C-S or TNC(part of TT)system

Frequency

50Hz

Residual current measure range

10mA ~ 3000mA

Output

Communication

RS485 interface, MODBUS-RTU protocol

   Alarm method

Sound-light alarm

SOE

20 alarm records,20 malfunction records,20 switching records

 Alarm set

Rated operation current value

300mA~1000mA(step size is 1mA)

 

Sound pressure of audio device

>70dB,<115dB(1m in front of the buzzer, A count)

Measurement accuracy

 

Residual current class1

Working power supply

AC/DC 85~270V, energy consumption≤ 5VA

Switching input

4-channel passive dry contact input (optocoupler isolation)

Relay output

Output method:2-channel relay normally open contact output, mechanical contact,contact capacity AC 220V/3A,DC 30V/3A

Power frequency withstand voltage

Among power supply with signal input,relay output and communication terminal, is 2 kV/min;

Among signal input with relay output and communication terminal, is 1.5 kV/min

Environment

Working temp:-10℃~+45℃;storage temp:-20℃~+70℃

Relative humidity:5%~95% without condensation;Altitude:≤2500m

 

 

Outline and dimension of ARCM200L shown in figure1:(unit:mm)

4.2  Installation method

Installation mode of ARCM200L type is embedded and the fixed mode is extruded, shown in figure 2.

 Figure 2

4.3 Wiring instructions(wiring is subject to the wiring diagram on the detector )

 4.3.1  Wiring method

Upper terminal: "12, 13" is the auxiliary power supply;"34, 35, 36" is relay output (DO1 is alarm output, DO2 is trip output);"24, 25, 26, 27, 28" is the on-off input;"21" and "22" are communications

J16 type wiring terminal:

Middle terminal: "53 ~ 64" is leakage current signal input (COM7, COM8, COM9, COM10 are not grounded)

4.4 Matters need attention

4.4.1 Connection method of residual current transformer

               Sheet 2

ATTN: as shown in the above table, when installing the residual current transformer, the N line and PE line must be strictly distinguished. In the three-phase four-wire system, the N line must run through the residual current transformer.The N wire passing through the residual current transformer shall not be used as PE wire, and shall not be repeatedly grounded or exposed to the conductor.PE wire shall not be used for residual current transformer.In TN-C system, the system must be modified to form local TT system, or transformed into TN-C-S system, and then connected according to the above table.

4.4.2 Auxiliary power supply connection

In combination with the above figure, when connecting the auxiliary power supply, the wire shall be made in the way as shown in figure 3. When making the wire, first press the wire head tightly, and then fix it with tin;The wiring is shown in figure 4. Insert it into the terminal row and tighten it with a screwdriver,to ensure the normal operation of the power supply.

 

4.4.3 Communication wiring

The device provides asynchronous half duplex RS485 communication interface, using modbus-rtu protocol, all kinds of data information can be transmitted on the communication line.Theoretically, up to 32 devices can be connected simultaneously on a single line, and each device can set its address and communication rate.It is recommended to use two core shielded wires with A diameter of no less than 0.75mm2, connected to A and B respectively. The shielding layer is connected to the ground or suspended at A single point. When wiring, the communication lines should be kept away from strong electric cables or other strong electromagnetic environment.

4.4.4 Sensor matching and installation

There are two kinds of external sensors, residual current transformer and temperature sensor, which are customized products and cannot be used to replace products of other manufacturers at will.When wiring, the secondary signal of residual current transformer does not distinguish the direction of current.

Packaging & Shipping

 Acrel ARCM200L-T16 multi channel electrical fire monitoring detector 16 channel temperature controller

 

Our Services

 

Company Information

 

You May Like

Find Similar Products By Category

You May Like

View More
Chat Now Contact Now