KPM83T LCD display digital overload overcurrent transformer protection relay
KPM83 series microcomputer comprehensive protection and measurement control devices is based on high-performance DSP processor and embedded real-time operating system, it is a protection and monitoring devices that integrated protection, monitoring and control, communications.
It is suitable for substations, power plants, industrial and mining enterprises, construction and other fields with voltage levels up to 35KV. It has such functions as protection, telemetry, remote mains, remote adjustment and remote control to achieve full control and management of it. , we can provide line protection and monitoring and control, transformer protection and control, motor protection and control, PT protection and control, capacitor protection and control, spare power source automatic throw-in device coupler protection and other product types.
KPM83T digital overload overcurrent transformer protection relay is mainly used for comprehensive protection, control and measurement of transformers with voltage levels of 35KV and below.
Product show for KPM83T transformer protection relay
Functions of KPM83T transformer protection relay
No. |
Protection function |
No. |
Protection function |
1 |
Quick-break |
6 |
High voltage zero-sequence overcurrent |
2 |
Overcurrent I |
7 |
Low voltage inverse time zero-sequence |
3 |
Overcurrent II |
8 |
PT disconnection |
4 |
Overload |
9 |
Non-power protection |
5 |
Inverse time overload |
10 |
|
Measurement and control functions of KPM83T transformer protection relay
- 14-way remote signaling is opened for collection;
- Remote control of circuit breaker, signal output (alarm signal, protection action signal, power-off signal, quick-break action signal, over-current action signal, zero-sequence over-current action signal, overload alarm signal, self-trip signal, high-temperature alarm signal);
- IA,IB,IC,Ua,Ub,Uc,la2,lb2,lc2,I01,I02,P,Q,F,COS medium analog; protection event sequence recording (SOE).
KPM83T transformer protection relay analog input
The input analog values are: protection currents la2, lb2, lc2, I01(high voltage side), I02 (low voltage side) for overcurrent protection and high voltage side zero sequence overcurrent protection; measuring currents IA, IB, ICfor current monitoring and power calculation; voltage Ua, Ub, Uc as low voltage blocking components and measuring voltage and power.
Technical parameters of KPM83T transformer protection relay
Index | Current fixed value | Time fixed value | fixed value error | Heat capacity coefficient | Prewarning heat capacity coefficient |
Content | |||||
Definite time overcurrent | 0.2In -20In | 0s- 60s | <5% | ||
Inverse time overload | 0.2In -20In | 0s- 60s | <5% | 10-2500 | 10-2500 |
definite time overload | 0.2In -20In | 0s- 60s | <5% | ||
High voltage zero sequence overcurrent | 0.2In -20In | 0s- 60s | <5% | ||
Low voltage zero sequence inverse time overcurrent | 0.2In -20In | 0s- 60s | <5% | 10-2500 |
KPM60 Low voltage motor protection relay | KPM75 Power quality analyzer | KPM53 Smart power meter |
KPM10 Smart power meter | KPM37 DIN rail smart power meter | KPM33 DIN rail smart energy meter |