Product Details

phase failure-sequence Phase-loss RelayTVR-2000C

Brand Name chfnad
Place of Origin China
Model Number TVR-2000c
Size Miniature
Usage Protective
Contact Load High Power
Protect Feature Sealed
Theory Electromagnetic Relay

Product Features

Key Specifications/Special Features

FunctionRated input voltage *Relay outputModel
Phase sequence and 
phase loss monitoring
3-phase, 3-wire 220 to 440 VACRelay:  1 NC,1 NOTVR-2000B
3-phase, 3-wire 380 to 660 VACRelay:  1 NC,1 NOTVR-2000C

* The power supply voltage is the same as the rated input voltage.

Ratings

Rated input voltage3-phase, 200 to 440 VAC (3-wire)
Input loadApprox. 2.6 VA
Operating 
time
Phase 
sequence
1 s±0.05 s
Phase loss0.1 s max. 
(when the voltage changes rapidly from 100% to 0% of rated voltage)
Indicators  LEDNormal: Green light; phase loss: Red light; Inverted: Yellow light
Output formRelay Output: SPDT contact 
Output relay ratingsRated load 
Resistive load 
5 A at 250 VAC 
5 A at 30 VDC 
Maximum switching capacity: 1,250 VA, 150 W 
Minimum load: 5 VDC, 10 mA (reference values) 
Mechanical life: 10 million operations min. 
Electrical life: 
5 A at 250 VAC or 30 VDC:50,000 operations 
3 A at 250 VAC/30 VDC:100,000 operations
Ambient operating 
temperature
-20 to 60°C (with no condensation or icing)
Storage temperature-25 to 65°C (with no condensation or icing)
Ambient operating 
humidity
25% to 85% RH (with no condensation)
Storage humidity25% to 85% RH (with no condensation)
Altitude2,000 m max.
Applicable wiresStranded wires, solid wires, or ferrules
Applicable wire size0.25 to 1.5 mm2 (AWG24 to AWG16)
Wire insertion force8 N max. for AWG20 wire
Screwdriver 
insertion force
15 N max.
Wire stripping length8 mm
Ferrule length8 mm
Current capacity10 A (per pole)
Number of 
insertions
50 times
WeightApprox.55g
MountingMounts to DIN Track, or screw mounting
Dimensions30 × 60 ×70 mm (W×D×H)

Specifications

Input frequency 
range
50 to 60 Hz
Phase loss detection 
level
80%±10% of rated input Calculation Formula 
= 1 – ((Highest phase-to-phase voltage – Lowest phase-to-phase voltage)/ 
Average three-phase phase-to-phase voltage)
Applicable 
standards
Conforming 
standards
EN 60947-5-1 
Installation environment (pollution level 2, Overvoltage category III)
EMCEN 60947-5-1
Insulation resistance20 MΩ min. 
Between external terminals and case 
Between input terminals and output terminals
Dielectric strength2,000 VAC for one minute 
Between external terminals and case 
Between input terminals and output terminals
Impulse withstand 
voltage
6 kV (between live terminals and exposed, non-charged metal parts)
Vibration resistanceFrequency: 10 to 55 Hz, 0.35-mm single amplitude 
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance100 m/s2, 3 times each in 6 directions along 3 axes
Degree of protectionTerminals: IP20

♦ Features

  – Three-phase monitoring of phase sequence, phase loss, and phase unbalance

  – Powered by the measuring circuit

  – 1 C/O contact

  – 3 LEDs for status indication

 

♦ Protective Functions

  – Phase sequence

  – Phase loss

  – Phase unbalance

 

♦ Typical Applications

    • Pumps     • Fans

    • Blowers    • Motors

    • Compressors

 

♦ Approvals

• CE   • rohs


You May Like