Product Details

Eja130a Pressure Transmitter price

Place of Origin Shaanxi, China
Brand Name YUNYI
Model Number Eja130a

Product Features

 

Eja130a Pressure Transmitter
DESCRIPTION:
1.EJA130Abe used to measure liquid, gas, or steam flow as well as liquid level, density and pressure

2.unmatched long-term stability.

3.The EJA Series is available with BRAIN, HART, FOUNDATION™ fieldbus or PROFIBUS PA communication protocols.
4.The high performance differential pressure transmitter model EJA130A can be used to measure liquid, gas, or steam flow as well as liquid level, density and pressure.
 It outputs a 4 to 20 mA DC signal corresponding to the measured differential pressure. 
 
FEATURES: 
Excellent performance and stability
The EJA series uses a silicon resonant sensor formed from monocrystal silicon, a perfect material which has no hysteresis in pressure or temperature changes.
The sensor minimizes overpressure, temperature change, and static pressure effects, and thus offers unmatched long-term stability.
Compact and light-weight design
Half the weight of conventional models thanks to miniaturization of the casing with the amplifier ASIC, pressure cell structure, and flange. The ASIC uses the minimum
 number of parts and improves the reliability of the amplifier.
Fieldbus communication capability
Fieldbus is a digital two-way communication system. It is a revolutionary technology for configuring instrumentation control systems and a promising successor to the standard 4 to 20 mA  analog communication used in most field instruments today.

TECHNICAL DATA: 

 EJA130A High Static Differential Pressure Transmitter
M CapsuleH Capsule
Range-100 to 100 kPa
(-400 to 400 inH2O)
-500 to 500 kPa
(-2000 to 2000 inH2O)
Span1 to 100 kPa
(4 to 400 inH2O)
5 to 500 kPa
(20 to 2000 inH2O)
Accuracy±0.065%±0.065%
Degrees of protectionIP67, NEMA 4X, and JIS C0920 immersion proof
CertificatesFM, CENELEC ATEX, CSA, IECEx
Output4 to 20 mA DC or FOUNDATION™ fieldbus or PROFIBUS PA 2-wire system with digital communication
Supply voltageBRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type)
Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model)
Ambient temperature-40 to 85 deg C (-40 to 185 deg F) (general use type)
-30 to 80 deg C (-22 to 176 deg F) (with integral indicator)
Process temperature-40 to 120 deg C (-40 to 248 deg F) (general use type)
Maximum working pressure32 MPa (4500 psi)
Mounting2-inch pipe mounting
Wetted parts materialCapsuleSUS316L (Diaphragm material is Hastelloy C-276)
Cover flangeSUS316
HousingCast aluminum alloy or SUS316 equivalent stainless steel (optional)