3095 differential pressure transducers
Description of differential pressure transducers:
differential pressure transducers accurately measures differential pressure, static pressure and process temperature. It dynamic calculators full remuneration mass rate. Traditional meters measure single process variables, but Rosemount 3095 Multi Variable flowrate transmitter measures all the process variables such as gas-flow rate used for calculating pressure and temperature compensation or liquid flow rate used for temperture compensation.
Specifications of differential pressure transducers:
Range | 0.5mH2O, 1mH2O, 2mH2O, 3mH2O, 5mH2O; |
Accuracy | 0.25%FS;0.5%FS |
Nonlinearity | 0.2%FS |
Stability | 0.2%FS/Y |
Output | 4-20mA(2 wire), 0-5V;0-10V(3 wire) |
Input voltage | 24(12~36)VDC (Amplify signal) |
Operating Temp | -40~80°C |
Compensated temp | 0~80°C |
Overload pressure | 150%FS |
Medium material | Housing: Stainless steel |
Explosion-Proof Grade | ExiaII CT4 |
Electric connection | Vented cable, insert screw thread ,insert flange type |
Protection Grade | IP68 |
Parameter of differential pressure transducers:
Measurement Type | Differential, Gage, Absolute, Level, Flow |
Output | 4-20mA HART (Revision 5), FOUNDATION™ Fieldbus, PROFIBUS PA |
Reference Accuracy | + 0.065% of span |
Total Performance | + 0.15% of span |
Long Term Stability | + 0.125% of URL for 5 years |
Rangedown | 100:1 |
Complete Specifications (3320KB) |