Product Details

power factor meter GH96L-E4/C

Place of Origin Shanghai, China
Brand Name Yasian
Model Number GH96/GH80/GH72
Measuring Current Range 5A
Measuring Voltage Range 110V/220V/380V
Accuracy Class 0.5class
Operating Temperature -10~55℃
Dimensions 96*96*90mm

Product Features

Specifications

Multi function power analyzer
measure I/U/kW/kWh/Kvar/Kvarh
and other electrical parameters
EN 61326:2006 EN 61010-1:2001

I. General

Network multi-function electric instrument is a multi-function electric instrument with programmable measurement,

display, digital communication and electric energy pulse transmitting output etc., which can complete electrical

measurement, electric energy measurement, data display, acquisition and transmission, and can be widely applied

to substation automation, distribution automation, intelligent building, electric energy measurement, management and

evaluation within the enterprise. Measurement accuracy is 0.5 grade, which can realize LCD site display and remote

RS-485 digital communication interface, and adopt MODBUS-RTU communication protocol.

Appearance Code

Name

Measurement

Display

Standard Function

Optional Function (combinable)

 

96 square

Network multi-function electric instrument

Three phase: U, I, P, Q, EP+, EP-, EQ+,

EQ-, S, F, PF or some parameters

LCD paging display

RS485 communication, electric energy pulse output

4DI, 4DO, 4AO, each single phase harmonic, voltage, current unbalance factor.

 

80 square

 

72 square

 

2DI, 2DO, 2AO, single phase harmonic, voltage and current unbalance factor.

 

II. Technical Parameters

 

Performance

Parameters

Input Measurement Display

Voltage

Network

Three phase three-wire, three phase four-wire

Rated value

AC 100V / AC 220V / AC 380V

Overload

1.2 times rated value (continuous); 2 times rated value/1s

Power

<0.4VA (per phase)

Impedance

>500kΩ

Accuracy

RMS measurement, accuracy grade is 0.5

Current

Rated value

AC 1A/5A

Overload

1.2 times rated value (continuous); 10 times rated value/1s

Power

<0.2VA (per phase)

Impedance

<2mΩ

Accuracy

RMS measurement, accuracy grade is 0.5

Frequency

45~65Hz

Power

Apparent power, active power accuracy is 0.5 grade, and reactive power accuracy is 1.0 grade

Electric energy

Four-quadrant metering, active power accuracy is 0.5 grade, and reactive power accuracy is 1.0 grade

Display

Programmable, switch-over, recycling (LCD) display

Power

Working range

AC/DC85~270V

Power consumption

≤5VA

Output

Digital interface

RS485 interface, Modbus-RTU protocol

Pulse output

2-way electric energy pulse output, pulse constant: 5000imp/KWh

Environment

Working environment

-10~55°C

Storage environment

-20~75°C

Safety

Withstand voltage

Input/power supply >2kV/1min, input/output >2kV/1min, power supply/output >1.5kV/1min(50Hz)

Insulation

Input, output, power supply to case >100MΩ

Electric energy measurement range

Electrical degree of measurement range for active power and reactive power is 0~999999Mwh, electrical degree exceeding the value shall be counted from 0.

 

III. Wiring Schematic Diagram

(Subject to physical wiring diagram)

72 square (overall dimension: 72*72*69.5 mm     Hole size:67*67mm)

power factor meter GH96L-E4/Cpower factor meter GH96L-E4/Cpower factor meter GH96L-E4/C