Specifications
12/110KV Polymer Insulator includes epoxy glass fiber rod, silicon rubber umbrella skirt mental parts.Product Description
12/110KV Polymer Insulator includes epoxy glass fiber rod, silicon rubber umbrella skirt mental parts.The company adopts the international advanced fitting press in technology and silicon rubber umbrella skirt once forming production. It is to improve the reliability of the composite insulator and production efficiency, and high strength, small size, light weight and beautiful appearance.
Note: special specifications can be users need to drawing production.
Main technical data | ||||||||
Type | Rated Voltage (KV) | Rated mechanical tensio load (KN) | Height (mm) | insulating distance Li. (mm) | Min norminal creepage distance (mm) | Diameter of Shed D. | 1 min power frequency wet withstand voltage not less than (KV) | Full wave lightning impulse voltage (peak value) (KV) |
FXBUW-12/70 | 12 | 70 | 390 | 180 | 460 | 98/88 | 42 | 105 |
FXBW-15/70 | 15 | 70 | 445 | 225 | 620 | 98/88 | 42 | 105 |
FXB-24/70 | 24 | 70 | 450 | 235 | 635 | 148/118 | 42 | 150 |
FXBOW-28/70 | 28 | 70 | 560 | 380 | 1250 | 88 | 95 | 230 |
FXBUW-33/70 | 33 | 70 | 560 | 380 | 1130 | 92/62 | 95 | 230 |
FXBUW-36/70 | 36 | 70 | 580 | 380 | 1250 | 88 | 95 | 230 |
FXBO-36/70 | 36 | 70 | 650 | 450 | 1320 | 148/118 | 95 | 230 |