Panel Earth Leakage Relay
1.Genneral
ASJ series earth leakage relays associated with a remote trip breaking device(automatic power breaking),provide the following functions:protection against indirect contact.limitation of leakage currents.Type Aearth leakage detection and power supplybreaking.Fully configurable:2 relays with configurable function(alarm or pre-alarm at 50% IΔn).
2.Technical Features
Technical Parameters | Value | |
Auxiliary power supply | Frequency | 45~63HZ |
Operating zone | AC110V/AC220±10% | |
Consmption | ≤5W | |
Insulation | Rated insulation voltage | 400 VAC |
Rated impulse voltage | 6kV | |
Degree of pollution | Class 3 | |
Threshold values | Accuracy of tripping | -20~-10% |
Domain of mains frequency | 50HZ/60HZ | |
Time delay setting | 0~10s | |
PRE-ALARM relay tripping | 50% | |
Hysteresis of the PRE-ALARM relay
| 20% |
3.Dimension
4.Typical Applications
Company Information
Packaging & Shipping
Packing
Shipping