Product Details

High Power Protection Relay Test System Set 220V / 2000VA K3063L

Brand Name Kingsine
Place of Origin China
Model Number K3063L

Product Features

Delivery Time:15 working days
Certification:ISO9001,CE

High Power Protection Relay Test System Set 220V / 2000VA K3063L

 1.Easy test
2.operation menu, Simple operation
3.Power:2000VA

  Friendly PC software for easy operation!

K30 series relay tester is extremely design for overseas user, with Friendly PC software as your need, unique features and functions helps you all the way!

1. Unique self-protection system assure the powerful protection when instrument is operating, automatic stop the output when the network is abnormal ;
2. Unique power switch and amplifier technology, so the output precision and power efficiency and factor are increased, which conforms to international tendency of energy save and environmental protection;
3. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
4. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
5. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A (Poleless and adjustable);
6. Function of transducer and energy meter testing (optional function);
7. Testing interface offer unique output monitoring function and Pre-curve-tracing function, helps more on the spot analysis;

Technical Data of K3063L

Voltage generators

Setting 

Range

4-phase AC (L-N)

4 x 0 ... 130 V 

2-phase AC (L-L)

2 x 0 ... 260 V

Power

4-phase AC (L-N)

4 x 70VA,  at 0 ... 130 V

2-phase AC (L-L)

2 x 110VA,  at 0 ... 260 V

Accuracy

<0.07% reading + 0.03% range guaranteed 

at 0 ... 130 V

<0.02% reading + 0.01% range typical 

at 0-130V

Resolution

1mV

Current generators

Setting 

Range

6-phase AC (L-N)

6 x 0 ... 30 A

3-phase AC (2L-N)

3 x 0 ... 60 A (Group A II B)

1-phase AC (3L-N)

1 x 0 ... 180 A 

Power

6-phase AC (L-N)

6x 450VA , at 0 ... 30A 

3-phase AC (2L-N)

3x 600VA,  at 0 ... 60A (Group A II B) 

1-phase AC (3L-N)

1 x 1500 VA,  at 0 ... 180A (Max.)

Accuracy

<0.07% reading + 0.06% range guaranteed at 0-30A 

<0.02% reading + 0.02% range typical at 0-30A

Resolution

1mA

Generators,  general

Frequency

Range

0 ... 1000 Hz

Accuracy / drift

Error < 0.001Hz at 10 ... 65Hz,

Error < 0.01Hz  at 65Hz...450Hz

Error < 0.02Hz  at 450Hz...1000Hz

Resolution

0.001Hz

Phase

Range

- 360° ... +360°

Accuracy / drift

Error < 0.2 °

Resolution

0.1°

Timer

Range

You May Like

Find Similar Products By Category

You May Like

View More