Product Details

Acrel 8 channel DC Multi-Circuits Monitoring Device AGF-M8T for PV Combiner Box 3.5KV Hall isolation

Product Features

Product Description

 Acrel 24 channels energy meter AGF-M24T DC0-20A solar string monitoring 0-1000V voltage measurement

 

 

General

 

AGF-T  Perforation  type  PV  confluence  acquisition  device  is specially designed for smart PV combiner box. It is used for monitoring the  running  state of solar  panels  in  solar cell arrays,  measuring the currents of solar cell, detecting the state of surge protection devices and DC    breaker.    The     device    is    equipped     with    RS485(Modbus)

communication port for transmitting all the datas to master device.

  

Product function

 Photovoltaic cell open circuit alarm to cooperate with group string voltage and judge Comprehensively

With 3-channel switching state monitoring to collect output idle contact information of  DC breaker ,lightning protector. protector etc

 Option  RS485  port,  Modbus-RTU  protocol;  programmable slave address, baud rate, data format

 English LCD display ,convenient to set parameters and check the data

Technical Parameters

 

Item

AGF-M4T

AGF-M8T

AGF-M12T

AGF-M16T

AGF-M20T

AGF-M24T

Input channels

4

8

12

16

20

24

Rated current

DC 0~20A

Response time

1s

Accuracy

0.5 class

Temperature coefficient

400ppm

RS485 communication

RS485/ModBus-RTU protocol,4800/9600/19200/38400bps

Additional function

 

Switch input

3-way input(optocoupler or dry contact mode)

General technical parameters

Temperature/ Humidity

Working temperature: -35~+65℃,   humidity95%,no

condensation, no corrosiongas place;

*Display module work temperature:-20~+70

Temperature

measurement function

To measure the inner temperature of box (-20℃~100℃)

Altitude

≤3000m

Insulation resistance

≥100MΩ

 

Industrial frequency

withstand

voltage

power/communication/switching input/cell voltage input--

AC 2kV/1min(When the auxiliary power supply is DC1500V, the   withstand voltage between the power supply, photocell input and other circuit is AC 2.7kV)Current input/power,cell voltage ,

communication,switching state—AC3.5kV/1min

 

 

 

 

EMC

GB_T 17626.2-2006;Electrostatic discharge immunity test 3rd grade, air discharge 8kV, contact discharge 6kV.

GB_T 17626.4-2008;Electrical fast transient immunity test grade 4, common mode 4kV, difference mode 2kV

GB_T 17626.5-2008;Surge(shock) immunity test grade 4, common mode 4kV, difference mode 2kV

GB_T 17626.8-2006;Power frequency magnetic field immunity test grade 4

 

Solar PV Power Distribution Monitoring Solution 

Acrel 24 channels energy meter AGF-M24T DC0-20A solar string monitoring 0-1000V voltage measurement

Practical Application of AGF-MxxT in PV Combiner Box