Product Details

Acrel ALP300-100/C Digital tube display protectorStrong anti-interference ability, stable and reliable work, digital,Intelligent

Product Features

ALP300 protector (hereinafter referred to as protector) adopts the latest single-chip microcomputer technology and has features of strong capacity of resisting disturbance, stable and reliable working, digitization and intellectualization and so on. The protector can protect the motor during operation in case of overtime starting, under-voltage, over-voltage, over-load, open phase, unbalance, under-load, ground/electric leak, blocking, short circuit and external faults and so on. The field maintenance personnel may rapidly find the fault cause with the digit display. The protector has RS485 remote communication interface and DC4~20mA analog quantity output to compose the network system with PLC and PC control units and to achieve remote monitoring of motor operation.

Features
Item
Parameter

Accuracy
Current: 0.5 class, Voltage:0.5 class

Auxiliary Power
AC 85V~265V/DC 110V~350 or AC 380V±10%, Consumption:15VA

Rated Voltage
AC220V / 380V / 660V,50Hz / 60Hz

Rated Current
1 (0.1A-999A)
Small special current transformer detection module
5 (0.1A-999A)
1.6(0.40A-1.60A)
6.3(1.6A-6.3A)
25(6.3A-25A)
100(25A-100A)
250(63A-250A)
External current transformer
800(250A-800A)
Relay output contact capacity
Resistance load
AC250V、6A
Switch Input
9 channel Inactive dry junction

Communication
MODBUS_RTU、PROFIBUS_DP

Enviroment
Working Temperature
-10ºC~55ºC
Storage Temperature
-25ºC~70ºC
Relative Humidity
≤95﹪
Altitude
≤2000m
Pollution Class
2 class

Protection Class
Main part: IP20;Display moudle: IP54

Installation Class
III

Rated current of motor protector(A)
current ratio setting
Transformer primary side turns
Setting current Is range(A)
Motor Power(kW)
1
able to set
5
0.1~999
0.12~250
5
1
0.1~999
0.12~250
1.6
unable to set
1
0.4~1.6
0.12~0.55
6.3
1
1.6~6.3
0.75~2.2
25
1
6.3~25
3~11
100
1
25~100
15~45
250
1
63~250
55~132
800
1
250~800
160~250
Optional Function

Code
Communication
Modbus-RTU
C
2 * Modbus-RTU
2C
Profibus
CP
Leakage Current Protection

L
Voltage Protection

U
Temperature Protection

T
4-20mA Analog Output

M
Time Protection

tE
Electrical Energy

EP
Undervoltage Restart

SU
Fault Recording

SR