Product Details

Acrel AIM-T300 AC/DC480V Ground Insulation Resistance Industrial Insulation Monitoring Self-test function, SOE event recording

Product Features

AIM-T300 insulation monitoring device is designed and developed by Acrel gathering the design experience of electric power meter industry for many years to monitor the insulation condition of low voltage IT distribution system (ungrounded system). The product adopts advanced micro controller technology, with high degree of integration, compact size and easy installation, and it integrates intelligence, digitalization and networking. The device, with many functions such as insulation fault warning, fault alarm, event recording and so on, can be used in the mines, glass factories, electric furnaces and test facilities, metallurgical plants, chemical plants, and exploded dangerous places, computer center, emergency power supply and other places to monitor the insulation status of IT system in real time. When insulation fault occurs, it will alarm and remind the staff to check the fault. The products conform to the requirements of enterprise standard Q/VDCL-26-2017 IT System Insulation Monitor.

2 Functional characteristics 2.1 Function of monitoring, fault warning and alarm the ground insulation resistance for IT system; 2.2 Multiple fault indication function, such as relay alarm output, LED alarm indication and so on. 2.3 Advanced field bus communication technology, communicate with the external alarm and display device or the upper computer management terminal and monitor the operation status of the IT system in real time. 2.4 Fault event recording function. It can record the time and type of failure to provide convenience for operators to query and analyze the operation status of the system and eliminate faults in time. 2.5 Applicable for insulation monitoring of AC, DC and AC / DC hybrid IT systems. 2.6 Self checking function. realize the fault self-inspection of instrument hardware circuit. 2.7 Broken line monitoring function. Monitor the connection condition between the L1/L2 and the IT system and the connection condition of the PE/KE function grounding wire.

Feature


Accessory power supply
Voltage
AC85-265V
Voltage range
 System voltage
AC/DC 0-480V
Frequency
50/60Hz
Frequency voltage
40-460Hz
Insulation monitoring
Measuring range
1K-5MΩ
Output
Relay output
Early warning, Alarm
Alarm range
10K-5MΩ
Environment
Working temperature
-10~+55℃
Response time (Ce=1μF)
<6s
Storage temperature
-20~+70℃
Measuring voltage
<20V
Relative humidity
<95%,without condensation
system leakage capacitance
<150μF
Altitude
≤2500m
Intemal parameters
Measuring current
<170μA
Communication
RS485,Modbus-RTU
Intemal DC impedance
≥120kΩ
Rated impulse voltage /Pollution Level
8kV/ⅢⅢ
Power dissipation
<8W
EMC/ Radiation
IEC61326-2-4

You May Like

Find Similar Products By Category

You May Like

View More
Chat Now Contact Now