Product Details

ACREL 300286 AIL100-8 insulation fault locator applied in insulation system

Brand Name Acrel
Place of Origin China
Model Number AIL100-8

Product Features

Product Description

Introduction

The medical IT system is mainly used in important Class 2 medical locations such as operating room, ICU/CCU
intensive care unit, providing safe, reliable and continuous power distribution for the important equipment at these
locations. Medical insulation monitoring and fault locating device is developed by the many years’ design experience
of the Acrel Electric in electric power meter industry, according to the special requirements of the insulation
monitoring and fault locating of the power distribution system in Class 2 medical locations. The products can realize
the real-time monitoring of insulation, load and temperature of isolation transformer in IT system, and have the
functions of system insulation fault loop positioning and centralized monitoring by multiple pieces of systems.
Products conform to the provisions of enterprise standard Q31/0114000129C013-2016 IT System Insulation
Monitoring Instrument.
Medical IT system insulation monitoring and fault locating products (seven-piece set) include AITR series
medical isolation transformer, AIM-M200 medical intelligent insulation monitoring instrument, AKH-0.66P26
current transformer, AIL100-4/AIL100-8 insulation fault locator, ASG100 test signal generator, DR-60-24 power
module and AID200 centralized alarm and display instrument, which are shown in Table 1.
2. Technical parameters ofASG100,AIL100-4/AIL100-8 test signal generator

Features

1. Insulation fault location in medical IT systems. 2. 4 or 8 channels with measuring current transformer per AIL100.
3. Up to 16 measuring channels can be combined by can bus in one
4. medical IT system.
6. A response time of up to 5 s in medical IT system acc. to IEC61557-9.

Dimension

Wiring

Typical connection

Technical parameter

Item
Model
AIL100-8
Power supply
Voltage
DC24V
Power consumption
≤2VA
Monitored system
Rated voltage
AC220V
rate frequency
45~60HZ
Locating signals
locating voltage
<25V a.c.r.m.s
locating current
<1mA r.m.s.
Fault locating
Maximum circuit
8 circuits
Response time
<2s
Communication
Mode
CAN communication
Protocol
self-defined protocol

Certificate

You May Like

Find Similar Products By Category

You May Like

View More
Chat Now Contact Now