Product Details

DC PV Photovoltaic Solar Energy 1000V Surge Devices

Place of Origin Hunan, China
Brand Name ZHONGPU SHENGDE
Model Number DXH06-F/3DC800R40

Product Features

DC PV Photovoltaic Solar Energy 1000V Surge Devices

 

1. APPLICATION

 

Designed especially for surge protection of the PV strings; apply to the PV power grid-connection system.

 

2.TECHNICALS PARAMETERS

 

Model DXH06-F/

3DC1000R40

3DC800R40

3DC600R40

Type (IEC 61643-1)

Class II /Type 2

Max. Continuous Operating Voltage(Uc)

1300VDC

1000VDC

800VDC

Nominal Continuous Operating                          Voltage(Un)

1000VDC

800VDC

600VDC

Nominal Discharge Current Capacity (In)

20kA(8/20μs)

Max. Discharge Current Capacity (Imax)

40kA(8/20μs)

Protection Mode

Full Mode Protection

Protection Level(Up)

≤4.0kv

≤3.6kv

≤3.2kv

Response Time(T)

<25ns

Fault Indicator

Available

Live Line(mm² )

≥6

Earth line(mm² )

≥10

Grounding Resistance(R)

≤4Ω

Protection Level of the Shell

IP20

Operating Temperature

-40~+70

Overall Size(mm)

54×90×65

Installation Method

35 mm DIN-rail

 

DC PV Photovoltaic Solar Energy 1000V Surge Devices 

3.NAMING RULES:

DC PV Photovoltaic Solar Energy 1000V Surge Devices4. WIRING DIAGRAM

 

DC PV Photovoltaic Solar Energy 1000V Surge Devices

 

 

DC PV Photovoltaic Solar Energy 1000V Surge Devices

 

5.Main Features:

 

l  Use Y-shaped connection, Full mode protection of the L+-L-/PE;

 

l  Use the temperature control circuit break protection technology,to avoid the accident;

 

l   With the remote alarm contact signal, convenient to remote monitoring of the system;

 

l   The module has normal and fault indication, with fast response speed and low residual voltage.

 

 

6.Installation Method and Attentions

 

1) Wiring as shown in Figure;

 

2) The connecting lead shall use many strands of copper wires of more than 6mm2, and the earth wire shall use many strands of copper wires of more than 10mm2. The connecting wire shall be as short, straight and coarse as possible. Grounding Resistance should be no less than 4Ω;

 

3) The front of lightning arrester shall be connected with proper fuse in series or be opened;

 

4) The power supply must be cut off while conducting the installation. It is prohibited to conduct the operation with the charge. The connecting lead must conform to the requirement;

 

5) After completing the installation, the lightning protection module shall be inserted tightly and inspected;

 

6) When there is RED for the fault indicator of the lightning arrester module (warning signal of remote-signaling port), it indicates that the lightning protection module has degraded and shall be replaced;

 

7) The SPD needn't special maintenance, but only check the connection and indicating state periodically.

 DC PV Photovoltaic Solar Energy 1000V Surge Devices

 

7. Certificates:

 

DC PV Photovoltaic Solar Energy 1000V Surge Devices

 

 

DC PV Photovoltaic Solar Energy 1000V Surge Devices