Din Rail Ac Power Meter AMC16Z-FAK48 Multi-circuit Energy Meter One RS485 Communication 48 Branch Full Electric Parameter

Brand Name Acrel
Place of Origin China
Model Number AMC16Z-FAK
Operating Temperature -10℃~45℃
Dimensions 180*90*45mm
Measuring Capacitance Range 0-999999 KWH
Measuring Voltage Range 220~264Vac L-N
Measuring Current Range 50mA AC (via -/50mA CTs)

Product Features

                                    AMC16Z-FAK Multi-circuit AC Data Center Energy Meter

AMC16Z series AC precision power distribution monitoring device is specially designed for data center server power management. The device is designed exquisitely and can provide A + B 2 incoming and 96 outgoing electrical parameters, the input and output switch, and the state of the lightning protection device with real-time monitoring. All alarm thresholds of measurement channels can be set separately. Over-outgoing triggers system acoustical warning immediately. A highly integrated monitoring loop is realized in the volume of traditional instruments.

● Monitoring: AC Outgoing Branch Circuits Multi-metering (1-phase & 3-phase)
 Measurement: Voltage, Current, Frequency, Active Power, Reactive Power, Power Factor and etc
● Power Quality: 2nd~31st&Total Harmonic
 Communication: RS485 (MODBUS-RTU)
 Rated Voltage: 220~264Vac L-N
 Rated Current: 50mA AC (via -/50mA CTs)
 Standard&Certificate: CE; IEC; LVD

Dual AC Outgoing Circuits Monitoring

● A+B Dual-side independent AC Circuits Monitoring

● Full Electrical Parameters Monitoring

● Outgoing Branch Circuits Multi-metering

Multiple Branch Circuits Metering

● Both 1-phase&3-phase Metering

● Max 36 circuits 1-phase

● Max 12 circuits 3-phase

● Mixed 8 circuits 3-phase and 12 circuits 1-phase for example

Power Quality Analysis

● 2nd~31st Harmonic

● Total Harmonic

Switch On/Off Status Detection

● A+B Dual Side

● 48-channel of DI (Digital Input)


1. Function Overview

FunctionDescription
Measurement(Common)

AC kWh, kVarh, Active Power, Reactive Power, Current, Voltage, Power Factor, Apparant Power, Frequency, Zero ground voltage, neutral line current

Measurement(Power Quality)

total harmonic content (THD), 2-31 harmonics

Temp.&HumidityMonitoring

Tempeatrue Monitoring Range: -40℃~+99℃

Humidity Monitoring Range: 20%~90%

AccuracyVoltage/current/active power/active energy level 0.5, reactive power/reactive energy level 1
Communication

RS485 Interface (MODBUS-RTU protocol)

DI(Swtich Input)48-channel DI (Digital Input); dry contact

2. Main Parameters

ParameterDescription&Value
Voltage
Input
Rated Voltage

3x220~264Vac L-N

Reference Frequency45~65Hz
Current
Input
Rated Current50mA AC (via -/50mA CTs)
Power
Supply
Source fromPower supply by AMC16Z-ZA;DC 12-24V when used alone
Installation
DIN-rail35mm standard DIN-rail Installation
Phase
Wiring
1P2W&3P4W1-phase 2-wire&3-phase 4-wire
Safety
InsulationAll terminals and the insulation resistance between the conductive pieces not less than 100MΩ
Withstand voltage
A-channel voltage and current signal // B-channel voltage and current signal //
other ports meet AC2kV 1min between pairs, leakage current should be less
than 2mA, no breakdown or flash over phenomenon.

3. Environment

ConditionDescription&Value
Temperature

Operating Temperature: -20℃+55℃;  Storage Temperature: -40°C ~+70°C

Humidity

≤95%RH,no condensation,without corrosive gas

Altitude

≤ 2000m


PIN overview of AMC16Z-FAK Data Center Energy Meter
PIN/Terminal Overview of AMC16Z-FAK48


Wiring Diagram of AMC16Z-FAK48 Data Center Multi-circuit Energy Meter
Voltage&Current Input Wiring of AMC16Z-FAK48 (Demo for A side partial wiring)