Product Details

DC to tested devices Protection Relay Test Set K3040i

Brand Name Kingsine
Place of Origin China
Model Number K3040i

Product Features

Delivery Time:15 working days
Certification:ISO9001,CE

1. Unique self-protection system assure the powerful protection when instrument is operating, automatic stop the output when the network is abnormal ;
2. Unique power switch and amplifier technology, so the output precision and power efficiency and factor are increased, which conforms to international tendency of energy save and environmental protection;
3. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
4. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
5. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A (Poleless and adjustable);
6. Function of transducer and energy meter testing (optional function);
7. Testing interface offer unique output monitoring function and Pre-curve-tracing function, helps more on the spot analysis;

Technical Data of K3040i

Voltage generators

Setting 

Range

4-phase AC (L-N)

4 x 0 ... 300 V 

2-phase AC (L-L)

2 x 0 ... 600 V

Power

4-phase AC (L-N)

4 x 110VA,  at 0 ... 300 V

2-phase AC (L-L)

2 x 220VA,  at 0 ...600 V

Accuracy

<0.07% reading + 0.03% range guaranteed 

at 0 ... 300 V

<0.02% reading + 0.01% range typical 

at 0-300V

Resolution

1mV

Current generators

Setting 

Range

3-phase AC (L-N)

3 x 0 ... 40 A

1-phase AC (2L-N)

1 x 0 ... 80 A 

1-phase AC (3L-N)

1 x 0 ... 120 A 

Power

3-phase AC (L-N)

3x 450VA , at 0 ... 40A 

1-phase AC (2L-N)

1x 520VA,  at 0 ... 80A 

1-phase AC (3L-N)

1 x 1200 VA,  at 0 ... 120A (Max.)

Accuracy

<0.07% reading + 0.06% range guaranteed at 0-40A 

<0.02% reading + 0.02% range typical at 0-40A

Resolution

1mA

Generators,  general

Frequency

Range

0 ... 1000 Hz

Accuracy / drift

Error < 0.001Hz at 10 ... 65Hz,

Error < 0.01Hz  at 65Hz...450Hz

Error < 0.02Hz  at 450Hz...1000Hz

Resolution

0.001Hz

Phase

Range

- 360° ... +360°

Accuracy / drift

Error < 0.2 °

Resolution

0.1°

Timer

Range

Infinite

Accuracy / drift

Error<0.1ms

DC generators

Voltage ranges

0 ... 300V/180W

Current ranges