Product Details

New Zealand AC output outlet 19" 1U 2KVA 2000Watt telecom power inverter CE / FCC Class B / LVDmade in Taiwan 2000W inverter

Place of Origin Taiwan
Brand Name Asian Electron Taiwan, YK
Model Number YK-PSW122KVA/E 242KVA/E 482KVA/E
Output Power Other, 2000W
Output Type Single
Size 408.7(L)X424.0(W)X44.0(H)mm
Weight 9kgs
Input Voltage 12/24/48VDC
Output Voltage 100/110/115/120V or 200/220/230/240V (switch selectable) RMS +/- 3%
Type Other, DC to AC as priority & AC to AC as spare
Output Frequency 50/60Hz +/- 0.05% (switch selectable)
Output Current 2000W

Product Features

 

Product Description

Features 

R Load Pure sine wave output (THD < 3%)

By pass function : DC to AC as priority & AC to AC as spare.

Output frequency: 50 / 60Hz switch

RS-232 interface / Wire connection to PC

Optional : SNMP / 2 sets dry contacts (voltage free) / AC to AC as priority & DC to AC as spare

Wired Remote control (optional)

Loading controlled cooling fan

Advanced microprocessor

Protection: Input Undervoltage,Input Overvoltage,Overload,Short circuit,Low battery alarm,Over temperature

AC output sockets : Universal / USA / Australia/New Zealand / Terminal / IEC

 

Specification

Model

Item

YK-PSW122KVAE

YK-PSW242KVAE

YK-PSW482KVAE

Continuous Output Power

1600W

1700W

1700W

Surge Rating

1870W/1Min, 2040W/20Sec

Input Voltage

12V

24V

48V

Frequency

50/60Hz ± 0.05% ( Switch Selectable)

Peak Output Current

11A

Efficiency (full load)

87%

90%

92%

No Load Current Draw

1.47A

0.8A

0.47A

Output Waveform

R Load Pure Sine Wave <3% THD

Output Voltage Regulation

200/220/230/240V(Switch Selectable) RMS±3%

P.F.

0.80

0.85

0.85

Input Voltage Range

10-16VDC

20-32VDC

42-62VDC

Protection

Overload, Short Circuit, Reverse Polarity (fuse), Input Undervoltage, Input Overvoltage,  

Over Temperature

Digital Display

OVP, UVP, OTP, OLP, VAC, AMP, WATT, VDC, TEMP, Hz

Safety

EN60950-1

EMC

 

EN 55022: 2010/AC: 2011(Class B)

EN 55024:2010

EN 61000-3-2:2006+A1:2009+A2:2009

EN 61000-3-3:2013

IEC 61000-4-2:2008

IEC 61000-4-3:2006+A1:2007+A2:2010

IEC 61000-4-4:2012

IEC 61000-4-5:2005

IEC 61000-4-6:2008

IEC 61000-4-8:2009

IEC61000-4-11:2004

Interface Control Port

RS-232 With Baud Rate 2400,4800, 9600, 19200 (Switch Selectable)

AC Input

220V AC

AC Frequency

(50Hz ~ 60 Hz)± 3%

Bypass

4~6ms

Operating Temperature Range

-20 °Cto 60°C

Storage Temperature Range

-30°C to 70°C

Dimensions

416.8(L) ×424.0(W) ×44.0(H) mm

Weight

9kgs

The wire gauge for AC input and AC output

#12

WARNING: The proper connection needs to be made in reference to line/neutral

 

 

Specification

Model

Item

YK-PSW122KVA

(1U)

YK-PSW242KVA

(1U)

YK-PSW482KVA

(1U)

Continuous Output Power

1600W

1700W

1700W

Surge Rating

1870W/1Min, 2040W/20Sec

Input Voltage

12V

24V

48V

Frequency

50/60Hz ± 0.05%( Switch Selectable)

Peak Output Current

25A

Efficiency (full load)

86%

88%

90%

No Load Current Draw

1.45A

0.7A

0.45A

Output Waveform

R Load Pure Sine Wave <3% THD

Output Voltage Regulation

100/110/115/120V(Switch Selectable)RMS±3%

P.F.

0.80

0.85

0.85

Input Voltage Regulation

10-16 VDC

20-32 VDC

42-62 VDC

Protection

Overload, Short Circuit, Reverse Polarity (Fuse), Over/Under Input Voltage,     Over Temperature.

Digital Display

OVP, UVP, OTP , OLP, VAC, AMP, WATT, VDC, TEMP, Hz

Safety

UL60950-1

(File No. E324561)

EN60950-1

 

 

 

EMC

 

 

 

 

 

FCC Class B

 

 

 

EN 55022:1998/ A1: 2000/A2:2003 (Class B)

EN 55024: 1998/ A1:2001/A2:2003

EN 61000-3-2: 2000/A2: 2005

EN 61000-3-3: 1995/A1: 2001

IEC 61000-4-2:1995/ A1:1998/A2:2000

IEC 61000-4-3:2002/A1: 2002

IEC 61000-4-4: 2004

IEC 61000-4-5:1995/A1: 2000

IEC 61000-4-6:1996/A1: 2001

IEC 61000-4-8:1993/A1: 2000

IEC 61000-4-11: 2004

Interface Control Port

RS-232 With Baud Rate 2400,4800, 9600, 19200 (Switch Selectable)

AC input

110V

AC Frequency

(50Hz ~ 60 Hz) ± 3%

Bypass

4~6ms

Operating Temperature

Range

-20℃ to 60℃

Storage Temperature Range

-30℃ to 70℃

Dimensions

416.8(L) ×424.0(W) ×44.0(H) mm

Weight

9 kgs

The wire gauge for AC input

and AC output

#12

WARNING: The proper connection needs to be made in reference to line/neutral

 

 

 

 

 

 

 

 

 

 

 

     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Company Information

We get many global accreditations, including ISO9001:2008, CE, FCC, LVD, UL, D&B, and E-Mark. Our products all meet RoHS related requirements.  All of our products are made in Taiwan and the main components are USA and Japanese brands.

 

Some of our inverters have digital display on front panel to show the inverter's working state, for example : OVP (DC over voltage protection), UVP (DC under voltage protection), OTP (inverter over temperature protection), OLP (inverter over load protection), VAC, AMP, WATT, VDC, TEMP, Hz.   All our inverters can be +/- 48VDC.  We have 200W 350W 700W 1000W 1500W 2000W 3000W 5000W inverters for selection.  Our inverters are suitable for car / ship / vehicles.....etc.  The inverters are also able to operate with renewable energy system to supply power. 

 

Packaging & Shipping

We pack products in good quality carton.  We cooperate with DHL / TNT, and forwarder for many years, so we can quote good transportation charges to customers.  If you want to let us handle the delivery, we will quote the delivery charge to you.

Our Services

 

We have R&D team to make OEM / ODM products.  We can provide the factory test report. 

You May Like

Find Similar Products By Category

You May Like

View More
Chat Now Contact Now