Specifications
Function of gen sets:Display voltage, current, power, power factor, battery voltage, speed, oil pressure and water temperature
Main technical performance parameter:
1.No-load voltage setting range:95--105%
2.Steady state voltage regulation rate:≤±1%
3.Transient state voltage regulation rate:≤-15%~20%
4.Voltage recover time:≤3s
5.Voltage fluctuation rate:≤±0.5%
6.Steady state frequency regulation rate:≤5%
7.Transient state frequency regulation rate:≤±10%
8.Frequency stabilization time:≤5s
9.Line -voltage waveform sinusoidal distortion rate:≤2.5%
Protection of when over speed,over water temperature, low oil pressure etc.
Main components for the gen sets:
Gas engine, alternator, control panel, common base, muffler etc;
Optional components:
Parallel equipment, soundproof, canopy.
Gas quality standard of Gas Generator
Gas type | Chemical formula | Restricted standards |
Methane | CH4 | More than 65% |
Ethane | C2H6 | Less than 6% |
Hydrogen | H2 | Less than 0.2% |
Propane | C3H6 | Less than 2% |
Butane | C4H10 | Less than 0.2% |
Other segregation of hydrocarbons | CxHy | Less than 2% |
Sulfureted hydrogen | H2S | Less than 0.01% |
Flammable substance |
| Less than 85% |
Remark: 1. Gas pleasure is between 5 to 10kpa
2. The lowest thermal value is 34.7MJ/m3