ARTON-08F
fire alarm control panel
EN54-2:2003
EN54-4:2003
Designed for centralized and stand-alone protection of various applications against fires and unauthorized intrusion by controlling statuses of up to 8 alarm loops.
FEATURES:
- each of panel’s loop can be adjusted as: fire alarm loop with verification, without verification, waiting for two detectors’ activation, intruder without delays, intruder with delays to input/output, intruder “hallway” type, intruder 24-hour monitoring.
- The panel defines and displays the following statuses of a fire alarm loop: “Standby”, “Attention” (verification of alarm loop or activation of the first detector), “Fire”, “Fault – SC”, “Fault – OC”, “AL disabled”.
- The panel defines and displays the following statuses of an intruder alarm loop: armed, disarmed, “Attention” – delay to input/output, “Alarm”, activation of detector in disarmed zone.
- Passive and active detectors can be interconnected to one AL, combined alarm loops can be constructed using 2- and 4- wire wiring diagrams.
- The possibility of changing the threshold deviation current in AL to determine detectors’ activation (separately for passive and active detectors).
- The possibility of construction of combined ALs with verification or expectation for 2 detectors activation and priority of manual call point‘s activation.
- 2 programmable powerful outputs “Out1” and “Out2” (300 mA current load) with programmable operation logics and operation options as power output of 4-wire AL, output to detector or incommutable power output of auxiliary devices (+12V).
- 4 programmable low-current outputs “K1”..”K4” (40 mA current load) that form output signals on combination AND/OR of “Fire” and “Fault” status in various ALs.
- The panel defines the following types of faults and statuses: short-circuit or open-circuit of AL, short-circuit of outputs, load break of outputs “Light”, “Sound”, “Fire”, “Fault”, no voltages powering outputs and AL, no 220 V power, fault of storage battery etc.
- 8 programmable authorized user access codes and 1 engineer access code.
- Possibility to assign rights for each user to control the certain AL.
- Possibility to change threshold current of determination of detectors’ activation in AL (separately for passive and active detectors).
- Module architecture optimizing the panel’s configuration. Auxiliary modules: BR4-4 blocking relays, BSKT-1 auto-dialing module through commutable telephone lines, BSKM-1 GSM-communicator, BSPC-1 computer coupler.
- Review of current configuration and programming (configurating) of the panel made from inbuilt keypad or from a computer using BSPC-1.
TECHNICAL SPECIFICATIONS:
Mains supply voltage | 220 (+22-33) V 50±1 Hz |
Battery size | 12±15%V 7Ahr |
Max AC power | 30 W |
Max storage battery current consumption | 1,2 A |
Standby AC power | < 17 W |
Standby operation time of the panel powered by the fully charged storage battery at mains outage | ≤24 hours, including ≥3 hours in the “Fire” mode |
Max number of circuits | 8 |
N.O. contact supply voltage | 15 (±1) V |
Output voltage at rated load | 12 (±2) V |
Total line resistance (not considering EOL resistor) | ≤220 Ohm |
Resistance of leakage between lines (EOL resistor disabled) and between each AL line and panel’s enclosure | ≥50 kOhm |
AL current interpreted by the panel as Open-circuit | from 0 to 3 mA |
AL current interpreted by the panel as Short-circuit | >25 mA |
Short-circuit limit current in AL | (28±2,8) mA |
the AL status change duration the panel responses to the AL status change duration the panel doesn’t issue the message about | ≥100 ms
≥50 ms |
Max number of active detectors (SPD-3, SPD-3.5, SPD-3.10, SPT-2B, SPT-3B etc.) interconnected to one loop. Max total current should not exceed 3 mA. | 32 |
Auto-reset time (disablement time) of AL at verification (set by a user) | 5-40 s |
Time of expectation for repeated triggering after AL resetting, the panel goes to the “Fire” mode on detecting it | 20-180 s |
Specifications of connectable bells, sounders and beacons | 12 (±2) V, 300 mA |
Max current load of “Out1” and “Out2” outputs | 300 mA |
Max current load of “Fire”, “Alarm”, “Fault”, “K1”-“K4” | 40 mA |
Meantime-between-failures | 30000 hours |
Average lifetime | 10 years min |
Dimensions | 300x240x100 mm |
Weight (storage battery excluding) | 3,5 kg |