Note the item parameter indicator
GF22020-6/-8 GF11040-8
Input rated voltage 380VAC + 20% three-phase AC
Output rating 20A/230V 40A/115V
Voltage regulation range 198 ~ 286V 99 ~ 143V
Output current limiting range 10%-105% rated current limiting point 105%
Voltage stabilization accuracy ≤0.5%
Steady flow accuracy ≤0.5%
Ripple coefficient ≤0.1%
Conversion efficiency ≥92% rated input and rated output
Dynamic response recovery time ≤200μs, overshoot ≤±5% 20% load jump to 80% load
Output short-circuit recoil current ≤40% rated current, recoverable
The output overvoltage alarm/can be set by the module monitoring module or monitoring module
Output overvoltage protection 295±5VDC, not recoverable 155±5VDC, not recoverable manually restore
Output undervoltage alarm/Set by the monitor
Input undervoltage protection 295±5VAC (recovery voltage 305±5VAC) After the AC voltage is normal,
Automatic recovery
Input overvoltage protection 465±5VAC (recovery voltage 455±5VAC)
Overtemperature protection 80℃±5 (temperature: 65℃±5) Automatic recovery after cooling
Cooling mode Temperature controlled air cooling
Overall dimensions 136mm×284mm× 455mm (width × height × depth)
Module net weight ≤15Kg
3.1.6.3 Appearance structure and interface of Air cooling module GF22020-6/-8 series
1. Shape and structure
Figure 3.1.31 GF22020-6/-8 Module appearance
Figure 3.1.32 GF22020-6/-8 Series module Front and rear views
2, input/output interface
The input and output signals of GF22020-6/-8 series modules shall be connected through the aviation socket at the rear, as shown in Figure 3.1.33, and the definitions of each foot are shown in Table 3.1.41:
Figure 3.1.33 Aviation Component Definition Diagram
Table 3.1.41 GF22020-6/-8 series Module socket definition Table
Signal name Pin number Signal definition
Ac input 1 Input terminal of the AC power supply of a phase module of the three-phase power supply. The input mode is three-phase three-wire system, and no phase sequence requirement is required
2 One phase of three phase electricity
3 One phase of three phase electricity
4 Protective ground The protective ground outlet of the PE module is connected to the module shell
Communication port 11 485A weak signal end, the communication interface between the module and the upper device is in serial asynchronous transmission mode, and the interface level is RS485
13 485B
Current sharing interface 17 Current sharing + weak signal end. When two or more modules output in parallel, this end needs to be connected in parallel to realize load sharing of modules; Suggestion: Use shielded cables for equalizing currents between layers
19 Current equalization - DC output
27 Output + GF11040 is: 26 and 27 Pin: Output +
Pins 28 and 29 are output -
28 Output -
Note:
1. In order to ensure safety, please ensure that the PE end of the protection ground in AC input is correctly connected to the ground;
2. To ensure system reliability, the three-phase AC input of each module must be configured with a separate incoming circuit breaker.