Product Details

Acrel LCD display Can connect to8 three-phase ACcircuits at the same time Power collection and monitoring device AMC200L-8E3/4G

Product Features

AMC200(L) DC multi-circuit intelligent power acquisition and monitoring device is mainly used for the full
electrical parameter measurement of multiple circuits, and can be connected to the current input of up to 12 single-phase
DC circuits at the same time. It can directly measure parameters such as voltage, current and power.


Features
Technical Parameter
Technical Indicator
Input
DC Voltage
One channel:DC -48V
DC Current
12 Channels Hall Current Sensor:Hall sensor secondary side DC 5V access
State Grid Monitoring
One channel:DC 0-5V
Overload
Voltage: 1.2 times for 1 second, 2 times for 1 second; Current: 1.2 times for 1
second, 10 times for 1 second
Frequency
Voltage,Current Class 0.5,Power Class 1.0
Resolution
The voltage output accuracy is 0.01V, the current output accuracy is 0.01A, the
power output accuracy is 0.01kW, and the power output accuracy is 0.01kWh
Function
Basic Function
Monitoring equipment system time, total voltage, total output current, total power, total electrical energy, voltage of each sub channel, current of each sub channel, power of each sub channel, electrical energy of each sub channel; RS485 communication
Alarm Function
DC voltage output too low alarm, DC voltage output too high alarm, one-time power-off alarm, module voltage loss alarm, metering sub channel error alarm, internal program error alarm, clock error alarm, memory unit failure alarm, AC input power failure alarm
Timing function
Support broadcast timing, remote timing calibration of metering module can be carried out through RS485 communication interface
Communication
Single-channel RS485, the default baud rate is 9600bps, and can be set to 1200-9600bps. Communication protocol: YD/T1363 protocol or Modbus RTU protocol
Hall power supply
A set of ±12V power output
Humidity And
Temperature
4 Channels NTC Temperature Monitoring:Temperature:-20-100℃
(Accuracy±2℃)
Humidity:20-90%RH(Accuracy ±5%RH)
Auxiliary
power
Voltage Range
DC -40V~-60V
Power consumption
The whole device≤2W (without Hall power supply output)
Storage
It has the storage function of historical energy data and historical alarm
information
Insulation resistance
≥40MΩ
Environment
Temperature
Working Temperature:-20℃~+60℃;Storage Temperature:-40℃~+70℃
Humidity
≤98% no condensation, no corrosive gas place
Altitude
≤4000m