APM800 Three Phase Multi-Function Energy Meter
The APM series meters are suited for measuring and displaying electrical quantities of electricity networks. The accuracy of active energy measurements corresponds to class 0.5S in accordance with the requirements of IEC62053-22.
The APM series meters offers many high-performance capabilities needed to meter and monitor an electrical installation in a compact 96 x 96 mm unit.All models include an RS-485 Modbus communication port, two digital input, two digital output,and alarming on critical conditions.The model of APM810 is able to perform current/voltage harmonics for assessment of the power quality. In addition the model of APM801 can offer the active energy accuracy up to class 0.2S.
Expand any model with field-installable option modules that offer a choice of additional digital inputs and outputs, analogue inputs and outputs, and Ethernet port.
Products Description
● True RMS Measurements
● Unbalance & Phase Angles
● Demands and Multi-Tariff energy
● Max/Min Log with Timestamp
● Alarms and SOE Logs
● External Option module
● 0.5-0.2S
● Alarms and SOE Logs
● External Option module
● Measure all electronic parameter(0.5S)
●neutral current unbalance,mean,extremum
● 2DI+2DO
● RS485(Modbus-RTU)Accuracy
Voltage、current and power:class 0.5S
Active power:class 0.5S
Reactive power: class 2
Frequency
Range:45-65Hz
Auxiliary power supply
AC/DC 85V~265V or AC/DC 115~415V
Pulse output
Output mode: Optocoupler pulse with open collector;
Pulse constant:4000(5A)、8000(1A) imp/kWh;
Consumption
Voltage:Power consumption:<0.5VA;
Current:Power consumption:< 0.5VA;
Auxiliary power supply:power consumption≤15VA
Installation
Panel mounted
Dimension(L*W*H)
Panel size(L×W):96*96mm
Cutout(L×W):92*92mm
Relay
3A/AC250V 3A/DC30V
Starting current
0.1%
Technical Parameter
Connection | 3 phase 3 wire, 3 phase 4 wire | ||
Frequency | 50Hz | ||
Input Voltage | Rated Voltage | AC 100V, 110V, 400V, 690V | |
Overload | 1.2 times rated value(continuous); 2 times rated value(1 second) | ||
Consumption | <0.5VA(per channel) | ||
Input Current | Rated Voltage | AC 1A, 5A | |
Overload | 1.2 times rated value(continuous); 2 times rated value(1 second) | ||
Consumption | <0.5VA(per channel) | ||
Accuracy | Voltage, current and power | Class 0.5S(APM800, APM810) Class 0.2S(APM801, APM830) | |
Active power | |||
Reactive power | Class 2 | ||
Harmonic | 1%(2-42nd), 2%(43-63rd) | ||
Switch inputs | Passive contact inputs, built-in power supply | ||
Relay outputs | Contact type: open contact in main part, changeover contact in module Pulse capacity: 3A/AC250V, 3A/DC30V | ||
Pulse output of energy | Output mode: Optocoupler pulse with open collector Pulse constant: 4000(5A), 8000(1A) imp/kWh | ||
Analog output | DC0-20mA, 4-20mA, 0-5V, 1-5V output, accuracy class 0.5%, Load resistance≤500Ω | ||
Analog input | DC0-20mA, 4-20mA, 0-5V, 1-5V input, accuracy class 0.5%, | ||
Storage card | Standard capacity: 4G, TF card up to 32G capacity | ||
Communication | RS485(Modbus-RTU), Profibus(Profibus-DP), Ethernet(Modbus-TCP, HTTP, DHCP) | ||
Auxiliary power supply | AC/DC 85~265V or AC/DC 115~415V | ||
Electromagnetic compatibility | IEC 61000 standard(Level 4) | ||
Environment | Operating temperature | -20~65℃ | |
Storing temperature | -20~70℃ | ||
Humidity | ≤95%(No condensation) | ||
Altitude | ≤2500m |