Product Details

Acrel ADL400 digital counter three phase smart electric energy meter With Interface RS485

Product Features

ADL400 Three-phase DIN Rail Energy Meter
ADL400 three phase electric meter is designed for three phase energy measurement on low voltage system.The meter meet the related technical requirements of electronic meter in the IEC62053-21,IEC62053-22 standards.
Products Description


● Measurement: 3-phase AC kWh, kVarh, U, I, P, Q, S, PF, F and etc
● Accuracy: 0.5% (kWh)
● Frequency: 45~65Hz
● Rated Voltage: 3x380~456Vac L-L (direct connect); 3x100~120Vac L-L (via PTs)
● Rated Current: 3x10(80)A AC (direct connect); 3x1(6)A AC (via CTs)
● Communication: RS485 (MODBUS-RTU)
● Multi-rate: 4 Tariff Rates and etc
● Data Function: Frozen Data,Max Demand,etc
● Harmonic: 2~31st and total Harmonic
● Standard&Certificate: IEC; CE;CE-MID; EAC
Diverse Electric Parameters Measurement
● kWh (3-phase positive Kilowatt-hours)
● kVarh (Kilovar-hours)
● Harmonic (2~31st voltage¤t)---Standard
● U (3-phase Voltage)
● I (3-phase Current)
● P (Power)
● Q (Reactive power)
● F (Frequency)
● S (Apparent power)
● PF (Power factor)
Multi-rate/Flexible Tariff
● 4 Time zone
● 4 Tariff rate (Spike, Peak, Flat, Valley)
● 2 Time period list
● 14 Time period by day
● Data Frozen (last 48 months or last 90 days)
● Max demand and occurrence time
HMI for Common Configuration
● PT or CT ratio
● Wiring methods (3P4W or 3P3W)
● Back linght time
● RS485 (MODBUS-RTU) communication setting
Technical Parameter
1.Function description
Function
Function description
Function provide
Measurement of kWh
Active kWh (positive and negative)
Reactive kWh (positive and negative)
A. B, C split phase positive active energy
Measurement of electrical parameters
U、I
P、Q、S、PF、F
Measurement of harmonics
2~31ST Voltage and current harmonic
LCD Display
12 bits section LCD display, background light
Key programming
3 keys to communication and set parameters
Pulse output
Active pulse output
Multi-tariff and functions
Adapt 4 time zones, 2 time interval lists, 14 time interval by day and 4 tariff rates

Max demand and occurrence time
Frozen data on last 48 months, last 90days
Date, time
Communication
Communication interface: RS485, Communication protocol: MODBUS-RTU

2.Technical parameter
Project
Performance parameter
Specification
3 phase 3 wires, 3 phase 4 wires
Measurement


Voltage
Reference voltage
3×100V3×380Vac、3×57.7/100Vac、 3×220/380Vac (Can normally work under 1.2 times of rated voltage)
Consumption
<10VA(Single phase)
Impedance
>2MΩ
Accuracy class
Error±0.2%
Currnt
Input current
3×1(6)A, 3×10(80)A
Consumption
<1VA Single phase rated current
Accuracy class
Error±0.2%
Power
Active, reactive, apparent power, error±0.5℅
Frequency
45~65Hz,Error±0.2%

Metering
Energy
Active energy(Accuracy class: 0.5) reactive energy(Accuracy class 2)
Clock
≤0.5s/d
Digit signal
Energy pulse output
1 active photocoupler output

Pulse
Width of pulse
80±20ms
Pulse constant
400imp/kWh,10000imp/kWh(Correspond with the basic current)
Communication
Interface and communication protocol
RS485:Modbus RTU
Range of Communication address
Modbus RTU:1~ 247;
Baud rate
1200bps~19200bps
Environment
Working temperature
-25℃~+55℃
Relative humidity
≤95℅(No condensation)
Wiring Illustration

PIN/Terminal Overview of ADL400 (Direct Connect Type)

3-phase 4-wire via direct connect

3-phase 3-wire via direct connect

PIN/Terminal Overview of ADL400 (CT Operated Type)
3-phase 4-wire CT operated
3-phase 3-wire CT operated
Dimension & Installation
(Current Input via Direct Connect)
(Current Input via CTs)
Solution Structure
Certification
Company Profile
FAQ

You May Like

Find Similar Products By Category

You May Like

View More
Chat Now Contact Now