ACREL 3 phase bus bar monitoring power meter with relay output for Closed busway system

Product Features

Product Description
ACREL 3 phase small bus bar monitoring power meter with relay output for data center
AMB smart bus detection unit of connection box is for power intelligent bus demand new design products, the test unit installation fixed inside the plug box, plug box adopts the unique way to the bus it integrated all electric power parameter measurement, such as single phase or three phase current, voltage, active power, reactive power, apparent power, frequency, power factor) and the electric power monitoring and assessment of the comprehensive management.
At the same time, it can monitor the temperature of bus interface in real time, and cooperate with the 2-way RJ45 communication interface (1 in 1 out) or LORA wireless communication.
Using modbus-rtu protocol, the monitoring data can be easily and reliably uploaded to the main control box and
background system to ensure the safe and reliable operation of the system. Intelligent bus bar plug box has the advantages of flexible wiring, which can replace the traditional centralized column head cabinet.
Functions and parameters
Functions of AMC16Z-FDK48 multi circuit DC energy power meter
*Measurement:3 phase voltage,current,frequency,active power,reactive power,power factor,active energy,reactive energy

*Rated voltage:AC 220V or 380V

*2-63st harmonics,1 circuit leakage current,8 channel temperature,1 channel humidity,max demand,zero line  current,neutral current, zero ground voltage

*2 channels DI , 2 channels DO
*Communication:1 channel RS485
Model
AMB100A
AMB110A
Measurement parameters
voltage, current, frequency, active power, reactive power, power factor, active power, reactive power
max demand,zero line current,neutral current, zero ground voltage
2-63st harmonics
1 channel leakage current,1 channel humudity
2 DI 2 DO
8 channel temperature
4 channel temperature
Voltage
Rated voltage
3x220VAC or 3x380VAC
Measurement range
±20%
Overload
Instantaneous voltage 2 times/second
Current
CT
5A/2.5mA
100A/20mA
Range
1%~120%
overload
Duration 1.2 times, instantaneous 10 times/second
Input frequency
45~60Hz
Accuracy
Class 0.5:Voltage/current/active power/active energy
Class 1:reactive power/reactive energy
Auxiliary power supply
Power on by system voltage
Communication
RS485/Modbus-RTU
Optional communication
LoRa communication
Installation
DIN 35mm din rail
Dimensions and wirings
Application