Product Details

Fire-retardnat Copper Conductor 4 core vvg power cable

Product Features

VVGnd Power Cable Copper/PVC/PVC Low Smoke Flame Retardant 

 

  

1. Cable's structure:

-Conductor-single or multistranded copper wire with cross-sections from 1.5 to 35.0 mm 

- insulation of conductors – PVC
- jacket – PVC
Application
The cable is used for transmission and distribution of electric power in stationary plants operated at 0.6 or 1 kV nominal AC voltage, 50 Hz frequency.
Requirements compliance
U U 31.3-05758730-024-2002, GOST 16442-80, IEC 502

Options
VVGng (flame retardant PVC jacket)
VVGnd (low smoke flame retardant PVC jacket)

2. Specification:

Type

Designation

Application

VV

Copper conductor ,PVC insulated ,PVC sheathed power cable

For laying indoors, in tunnel or cable trench,unable to bear extermal mechanical forces. Single core cable is not permissible to lay in magnetic duct

VLV

Aluminium conductor ,PVC insulated ,PVC sheathed power cable

VY

Copper conductor, PVC insulated, PE sheathed power cable

VLY

Aluminium conductor ,PVC insulated ,PE sheathed power cable

VV22

Copper conductor ,PVC insulated ,steel tape armoured ,PVC sheathed power cable

For laying indoors, in cable trench or direct in ground ,able to bear external mechanical forces, but unable to bear pulling force

VLV22

Aluminium conductor ,PVC insulated ,steel tape armoured ,PVC sheathed power cable

VV23

Copper conductor ,PVC insualted ,steel tape armoured ,PE sheathed power cable

VLV23

Alunminium conductor ,PVC insulated ,steel tape armoured ,PE sheathed power cable

VV32

Copper conductor, PVC insulated, steel wire armoured,PVC insulated power cable

 

For laying indoors, in cable or direct in ground ,able to bear external mechanical forces, but unable to bear large pulling forces

VLV32

Aluminium conductor, PVC insulated ,steel tape armoured ,PVC sheathed power cable

VV33

Copper conductor, PVC insulated steel wire armoured , PE sheathed power cable

VLV33

Aluminium conductor , PVC insulated , streel wire armoured ,PE sheathed power cable

Note: The armoured single core cables is only used for D.C.system. As for A.C.system,non-magnetic armored material should be applied

Fire-retardnat Copper Conductor 4 core vvg power cable

 

 

3. Nominal Cross-sectional Areas:

1.5 mm2 , 2.5 mm,4 mm2 , 6 mm2 , 10 mm, 16 mm2 ,25 mm, 35 mm2 , 50 mm,70 mm, 95 mm,120 mm,150 mm2 ,185 mm,240 mm2 ,300 mm2  400 mm2 500 mm2 630 mm2 800 mm2

  Fire-retardnat Copper Conductor 4 core vvg power cable

4. Production Range:

single core cable from 1.5 mmto 800 mm2,muli-core cable from 1.5 mm2   to 400 mm2

  Fire-retardnat Copper Conductor 4 core vvg power cable

5. Operating Characteristics:

Rated power-frequency voltage u0/u:0.6/1 KV

Max permissible continuous operating temperature of conductor 70

Max short-circuit temperature of the conductor shall not exceed (Max 5 seconds duration): cross-section of conductor  300 mm2

 

The ambient temperature under installations should not be below 0

 

The bending radius of single core cable should not be less than 20 times of the cable diameter ,the bending radius of multi-core cable should not be less than 15 times of the cable diameter.

 