Specifications
1.Plastic insulatedcontrol cable2.Rated voltage:450/750V
3.We are manufacturer
4.Best price and high quality
KYYP-23/KYJYP-23-Copper conductor PE/XLPE insulated and PE sheathed braided shield steel-tape armored control cable
Specifications
1.Plastic insulatedcontrol cable
2.Rated voltage:450/750V
3.We are manufacturer
4.Best price and high quality
This product is suitable for connections for all kinds of electrical equipment and instruments for control and monitoring as well as ground circuits with rated voltage up to 450/750V. We produce numerous cables with various combinations of fire resistant features such as flame retardant control cables, fire resistant control cables, low-smoke low-halogen or low-smoke halogen-free flame retardant control cables
The operative standard for this product is GB/T9330. We can also supply cables conforming to IEC, DIN, and BS standards.
Performance of use
Rated voltage U0/U: 450/750V
The Max. long-time permitted operating temperature is 70°C for PVC or PE insulated cable, 90°C for XLPE insulated cables.
The allowable bending radius for installation shall not be less than 6 times of the outer diameter for non-armored or shielded flexible cables, and not less than 12 times of the outer diameter for armored or copper tape shielded cables.
Main technology performance specification
DC electrical resistance of conductor and insulation resistance at 20°C shall be according to GB/T9330
Cables shall be able to withstand AC VOLTAGE at 3000V for 5 minutes.
Flame retardant control cables shall pass the category A, B or C burn test as specified in GB/T18380
Fire resistant control cables shall pass tests as specified in GB/T19216
Low-smoke low-halogen or low-smoke halogen-free control cables shall meet the test requirements of GB/T18380, GB/T17650, GB/T17651 as required.
Type | Name | Scope of manufacture | Application environment | |||
Nominal No. of cores of conductor | ||||||
0.75/1/ 1.5/2.5 | 4/6 | 10 | ||||
cores | ||||||
KYYP-23 KYJYP-23 | Copper conductor PE/XLPE insulated and PE sheathed braided shield steel-tape armored control cable | 7-61 | 4-61 | 4-10 | For laying in fixed places, such as indoors, in trenches or ducts with shield requirements and where the cable is able to bear a lot of external mechanical loads. |
Note
We can produce all kinds of control cables in addition to the general control cables as above, such as flame retardant control cables, fire resistance control cables, low-smoke low-halogen or low-smoke halogen-free flame retardant control cables.Type of cables are as shows:
l Type of flame retardant control cables shall be plus ZA, ZB, ZC before type of general control cables;
l Type of fire resistance control cables shall be plus N before type of general control cables;
l Type of low-smoke low-halogen or low-smoke halogen-free control cables shall be plus DDZA, DDZB, DDZC or WDZA, WDZB, WDZC before type of general cables.