■ Rated current: 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
■ Rated working voltage: 110V, 230V ~ (1P, 1P + N), 400V ~ (2 ~ 4P, 3P + N)
■ Isolation
□ Mechanical contact indication window, realistic cut-off instructions
□ The window is green and the contact is in the open state. The window is red and the contact is in the closed state
■ Impulse withstand voltage: 4kV
■ Max withstand current: 6kA Circuit Breaker
■ Mechanical life: 20,000 times
■ Electrical life: 10000 times
■ Ambient temperature
□ Use ambient temperature: -5℃~+40℃
■ Wiring
□ Tunnel type terminal block
□ Terminal area: 1 ~ 63A, for the wire of 25mm ² and below
■ Accessories
□ OF auxiliary contact, SD alarm contact, MX + OF shunt release, MV over-voltage release, MN undervoltage release, MV + MN over-voltage release
■ Tripping characteristics
□ Type B curve
Protect load of smaller short-circuit current (such as power supply, long cable, electric motorized vehicles, etc.)
Tripping characteristics: instantaneous trip range (3-5) In
□ Type C curve
Protect conventional load and distribution cables (such as home lighting boxes, power distribution boxes, etc.)
Tripping characteristics: instantaneous trip range (5-10) In
□ Type D curve
Protect impact load with the large starting current (such as motors, power counters, transformers, etc.)
Tripping characteristics: instantaneous trip range (10-14) In
■ Installation method:
□ Mounted on the TH35-7.5 steel rail.
Circuit breaker power consumption per pole
Rated current In(A) | Maximum power consumption per pole(W) |
1~10 | 2 |
16~32 | 3.5 |
40~63 | 5 |
Rated short - circuit breaking capacity
Rated current(A) | Tripping curve |
B | C | D |
1~40 | 6KA | 6KA | 6KA |
50,63 | 6KA | 6KA | 6KA |
Mechanical Electrical Life
Category | Time | Operating frequency(time/h) | Rated current A |
Electrical life | 10000 | 240 | 1~32 |
120 | 40~63 |
Mechanical life | 20000 | 240 | 1~63 |
Over-current protection characteristics (reference temperature 30 ℃)
No. | Trip type | Rated current(A) | Initial state | DC | Set time | Prosrective result | Remark |
a | B, C, D | 1~63 | Cold | 1.13In | t≤1h | Non tripping |
|
b | B, C, D | 1~63 | After the last | 1.45In | t<1h | Tripping | The current rise steadily to a fixed value within 5S |
c | B, C, D | In≤32A | Cold | 2.55In | 1s<t<60s | Tripping |
|
In>32A | 1s<t<120s |
|
d | B | 1~63 | Cold | 3In | t≤0.1s | Non tripping |
|
5In | t<0.1s | Tripping |
|
C | 5In | t≤0.1s | Non tripping |
|
10In | t<0.1s | Tripping |
|
D | 10In | t≤0.1s | Non tripping |
|
14In | t<0.1s | Tripping |
|
Tripping characteristic curve
Temperature(℃) Corrected current value(A) Rated current(A) | -35 | -30 | -20 | -10 | 0 | 10 | 20 | 30 | 40 | 50 | 60 | 70 |
1 | 1.3 | 1.26 | 1.23 | 1.19 | 1.15 | 1.11 | 1.01 | 1 | 0.96 | 0.93 | 0.88 | 0.83 |
2 | 2.6 | 2.52 | 2.46 | 2.38 | 2.28 | 2.2 | 2.08 | 2 | 1.92 | 1.86 | 1.76 | 1.66 |
3 | 3.9 | 3.78 | 3.69 | 3.57 | 3.42 | 3.3 | 3.12 | 3 | 2.88 | 2.79 | 2.64 | 2.49 |
4 | 5.2 | 5.04 | 4.92 | 4.76 | 4.56 | 4.4 | 4.16 | 4 | 3.84 | 3.76 | 3.52 | 3.32 |
6 | 7.8 | 7.56 | 7.38 | 7.14 | 6.84 | 6.6 | 6.24 | 6 | 5.76 | 5.64 | 5.28 | 4.98 |
10 | 13.2 | 12.7 | 12.5 | 12 | 11.5 | 11.1 | 10.6 | 10 | 9.6 | 9.3 | 8.9 | 8.4 |
16 | 21.12 | 20.48 | 20 | 19.2 | 18.4 | 17.76 | 16.96 | 16 | 15.36 | 14.88 | 14.24 | 13.44 |
20 | 26.4 | 25.6 | 25 | 24 | 23 | 22.2 | 21.2 | 20 | 19.2 | 18.6 | 17.8 | 16.8 |
25 | 33 | 32 | 31.25 | 30 | 28.75 | 27.75 | 26.5 | 25 | 24 | 23.25 | 22.25 | 21 |
32 | 42.56 | 41.28 | 40 | 38.72 | 37.12 | 35.52 | 33.92 | 32 | 30.72 | 29.76 | 28.16 | 26.88 |
40 | 53.2 | 51.2 | 50 | 48 | 46.4 | 44.8 | 42.4 | 40 | 38.4 | 37.2 | 35.6 | 33.6 |
50 | 67 | 65.5 | 63 | 60.5 | 58 | 56 | 53 | 50 | 48 | 46.5 | 44 | 41.5 |
63 | 83.79 | 81.9 | 80.01 | 76.86 | 73.71 | 70.56 | 66.78 | 63 | 60.48 | 58.9 | 55.44 | 52.29 |
Current correction factor used at different altitudes
Trip type | Rated current(A) | Current correction factor | Example |
≤2000m | (2000~3000)m | ≥3000m |
B, C, D | 1, 2, 3, 4, 6, 10, 15, 20, 25, 32, 40, 50, 63 | 1 | 0.9 | 0.8 | Rated current used after the product of rated current of 63A derates capacity in 2500m:0.9x63=56.7A |
Wiring installation
Current grade(A) | Screw | Rated torque(N·m) | Ultimate torque(N·m) | Standard torque(N·m) |
1~63 | M5 | 2.5 | 4.5 | 2.0 |
Wiring:25mm2 and below wire connection, wiring method is screws to tighten the wiring, the torque is 2.5N · m.
Rated current In(A) | Copper conductor nominal cross-sectional area(mm²) |
1~6 | 1 |
10 | 1.5 |
16、20 | 2.5 |
25 | 4 |
32 | 6 |
40、50 | 10 |
63 | 16 |