Specifications
LPG tank volume 20-100M3 Design pressure 1.78MpaTank materail Q345R
Type LPG tank
Thickness 14mm
10 m3 Main devices configuration table of skid-mounted filling station | ||||
No. | Name of Devices | Specification | Unit | Quantity |
1 | Storage tank | 10m3 | set/sets | 1 |
2 | Base and platform | 4000*2000*200mm | set/sets | 1 |
3 | Dispenser | JDK50 LLarge touch screen, | set/sets | 1 |
4 | Nitrogen cylinder | φ219 | piece/pieces | 1 |
5 | Gas cylinder regulator | YQD-09 | set/sets | 1 |
6 | Anti-explosion connection box | Terminal 20A24 | set/sets | 1 |
7 | Stainless steel spherical valve | ZG3/4 | piece/pieces | 2 |
8 | Copper spherical valve | G1/4 | piece/pieces | 2 |
9 | Spray line | DN25 | set/sets | 1 |
10 | Staircase | Circular tube φ16 | set/sets | 1 |
11 | Combustible gas alarm | RB10-2 | set/sets | 2 |
12 | Filling pump | LF2G-8 | set/sets | 2 |
13 | Damping pressure gage | Y-100 0~2.5 Mpa | piece/pieces | 4 |
14 | Temperature gage | —40°C~+80°C | piece/pieces | 2 |
15 | Liquidometer | DN20 L=1800 | set/sets | 2 |
16 | Stop valve | DN80 J41N-40 | piece/pieces | 2 |
17 | Stop valve | DN50 J41N-40 | piece/pieces | 4 |
18 | Stop valve | DN20 J41N-40 | piece/pieces | 2 |
19 | Spherical valve | DN50 Q41F-40 | piece/pieces | 10 |
20 | Spherical valve | DN25 Q41F-40 | piece/pieces | 4 |
21 | Spherical valve | DN15 Q41F-40 | piece/pieces | 3 |
22 | Quick action emergency valve | DN50 QDY641F | piece/pieces | 2 |
23 | Damping pipe | DN50 | piece/pieces | 4 |
24 | Percolator | DN50 Y907-40 | piece/pieces | 2 |
25 | Safety valve | DN80 A42F-25 | set/sets | 2 |
26 | Safety return valve | DN50 AH42F-25 | set/sets | 2 |
27 | Spawning valve | DN15 A21F-25 | set/sets | 1 |
28 | Dispenser connecting pipe | DN50 8m | piece/pieces | 1 |
29 | Dispenser connecting pipe | DN25 8m | piece/pieces | 1 |
30 | Controller cabinet | – | set | 1 |
SKID SBT-5.1 units for LPG with the following characteristics:
- LPG tank capacity of 4.85 m3 equipped approved by TÜV CROATIA
with complete armor: a safety valve REGO 5/4" with check device with
everseal, level indicator Rochester, filling valve with automatic termination
charge of 80%
- Tatsuno loading unit, with a single display, CE1026 Guideline 94/9/EC -
ATEX, Ex II 2G IIA T3, capacity 50 l/min
- Blackmer pumping units KLGL 1.5 defined by the ATEX directive
94/9/EC, the Ex engine performance power 3 kW signed Exde IIC T4,
capacity 80 l / min
- Pipe installation with all the necessary elements for the installation in
accordance with attach VII of directive 97/23/CE: relief valve, filter, excess
flow valves, check valves, solenoid valve coil in Ex design, safety valves,
pressure gauges with check device with everseal
- Fully assembled on a metal base with electrocabinet for electrical
connection of the consumer, ready for assembly on site
Specification portable unit for charging vehicles for LPG
LPG tank volume 4.98 m3:
- 2000 kg load capacity
- design pressure of 16.7 bar
- test pressure 25 bar
- A type of cylindrical, horizontal with two saddle
- placed on a steel pedestal
- drawn up in accordance with the PED Directive (97/23/EC)
Connections to the tank and fittings:
- filling up with non-return valve
-the safety valve and check device with everseal
- condensate drain from the bottom side with a block valve
and plug
- level gauge
- return of the gas phase and the aggregates with nonreturn
valve and ball valve wafer-typ
- return of the liquid phase with bypass valve with check
valve and ball valve wafer-typ
- outlet flanged equipment for car filling station
- pumping unit Blackmer + electromotor in Ex protection II 2G EEx de IIC T4
- pipe fittings Sacigas
- safety equipment Rego
- loading unit Tatsuno Europe (other on request)
Equipment approved by TÜV CROATIA