Silent Canopy 45kw / 56kva three phase Generator set powered by Cummins diesel engine

Brand Name NFCase
Place of Origin China
Model Number AIA-1

Product Features

Delivery Time:3-5 days
Certification:CE,FCC,MSDS

Technical Specifications : 

Genset

Prime Power (kw/kva)

45/56

Standby Power (kw/kva)

50/63

Voltage Recovery Time

≤1S

Rated Current (A)

81

Rated Frequency (Hz)

50

Frequency Recovery Time

≤5S

Running Noise db(A)/7m(Silent type)

75

Battery capacity (V-Ah)

24V 100Ah

Fuel Tank Capacity(L)

100

Engine

Engine brand

Cummins

Output Power (kw)

50

Cylinder No. & Config.

4, in-line

Combustion System

direct injection

Compression Ratio

16.5:1

Displacement (L)

3.9

Bore X Stroke (mm)

102*120

Engine Speed (r/min)

1500

Speed Governing

Mechanical

Starting System

24V DC Electric

Filter System

Dry oil filter/Fuel filter/Oil filter

Cooling system

Water-cooled

Alternator

Alternator brand

Stamford, Mecc-alte,Faraday…

Excitation System

Brushless, self-exciting

Voltage Regulation Mode

AVR

Connection Type

3phase,4wires,”Y” connection

Pole No.

4

Rotation Speed (r/min)

1500

Temperature Rise (℃)

125

Insulation class

H

Voltage Regulation (0 load)

≥95%~105%

Protection Grade

IP23

Generator soundproof/Silent and canopy

1) Excellent ventilation

2) Black finish stainless steel locks and hinges

3) Zinc plated or stainless steel fasteners

4) Body made from steel components treated with polyester powder coating

5) Two large doors on either side

6) Radiator fill access plate

7) Fully guarded cooling fan and battery charging alternator

8) Fuel fill and battery access via lockable access doors

9) Emergency stop button on canopy exterior

10) Lube oil drain and radiator drain to exterior

11) Control panel viewing window

12) Lifting points on base frame

Our Picture :

Our advantages :
1.Inspection

1) Each engine shall be tested at manufacturer’s workshop to certify the engine output according to present standard and fuel consumption in accordance with the site operating condition specified by purchaser on the specification datasheet.

2) All relevant information drawings pertinent to the testing and test procedure shall be transmitted to the purchaser in advance of the test date notification.

3) All accompanied documents are corresponding to the actual situation of generators, includin