Product Details

2-Zone Conventional Fire Alarm Control Panel

Place of Origin Ukraine
Brand Name ARTON
Model Number ARTON-02F
Usage Fire

Product Features

ARTON based in Chernivtsi, Ukraine began over 13 years ago. Our founder and CEO has an engineering background and strong working knowledge of plastic moulding, electrical and optical devices construction. He saw the perspective in the security industry by the rapid growth. ARTON under his leadership has grown from its small beginnings to become the leading brand in its field. ARTON designs, manufactures and markets fire alarm and security devices (conventional photoelectric smoke, heat, combined detectors, manual call points, fire alarm control panels, intruder detectors, accessories etc.).

 

Product Types:

1. Fire Detectors

2. Fire Alarm Control Panels

3. Accessories, etc.

 

2-Zone Conventional Fire Alarm Control Panel:

ARTON-02F

fire alarm control panel

EN54-2:2003

EN54-4:2003

 

Designed for centralized and stand-alone protection of various applications against fires and unauthorized intrusion by controlling statuses of up to 2 alarm loops.

 

FEATURES:

  • each of panel’s loop can be adjusted as: fire alarm loop with verification, without verification or waiting for second detectors’ activation.
  • The panel defines and displays the following statuses of a fire alarm loop: “Standby”, “Attention” (verification of alarm loop or activation of the first detector),  “Fire”, “Fault – SC”, “Fault – OC”, “AL disabled”.
  • Passive and active detectors can be interconnected to one AL, combined alarm loops can be constructed using 2- and 4- wire wiring diagrams.
  • The possibility of changing the threshold deviation current in AL to determine detectors’ activation (separately for passive and active detectors).
  • The possibility of construction of combined ALs with verification or expectation for 2 detectors activation and priority of manual call point‘s activation.
  • Sounder-beacon output with ≤500 mA load current.
  • 2 programmable powerful outputs “P1” and “P2” (≤200 mA current load) with programmable operation logics and operation options as 4-wire AL power output, detector output or incommutable power output of auxiliary devices (+12V).
  • The panel defines the following types of faults and statuses: short-circuit or open-circuit of AL, short-circuit of outputs, load break of outputs “Light/Sound”, “Fire”, “Fault”, no voltages powering outputs and AL, no 220 V power, fault of storage battery etc.
  • 2 programmable user access codes and 1 engineer access code.
  • Possibility to assign rights for each user to control the certain AL.
  • Slot for auxiliary modules’ connecting. Auxiliary modules: BR4-4 blocking relays, BSKT-1 auto-dialing module through commutable telephone lines, BSKM-1 GSM-communicator, BSPC-1 computer coupler.
  • Review of current configuration and programming (configurating) of the panel made from inbuilt keypad or from a computer using BSPC-1.

 

TECHNICAL SPECIFICATIONS:

Mains supply voltage      

187-242 V AC  50±1 Hz

Battery size 

12±15%V 7Ahr

Max AC power

30 W

Max storage battery current consumption

1,0 A 

Standby AC power

< 15 W

Standby operation time of the panel powered by the fully charged storage battery at mains outage

≤24 hours, including ≥3 hours  in the “Fire” mode

Max number of circuits

2

N.O. contact supply voltage

15 (±1) V

Output voltage at rated load

12 (±2) V

Total line resistance (not considering EOL resistor)

≤220 Ohm

Resistance of leakage between lines (EOL resistor disabled) and between each AL line and panel’s enclosure

≥50 kOhm

AL current interpreted by the panel as Open-circuit

from 0 to 3 mA

AL current interpreted by the panel as Short-circuit

>20 mA

Short-circuit limit current in AL

≥24 mA

the AL status change duration the panel responses to

the AL status change duration the panel doesn’t issue the message about

≥80 ms

 

≥50 ms

Max number of active detectors (SPD-3, SPD-3.5, SPD-3.10, SPT-2B, SPT-3B etc.) interconnected to one loop.

 Max total current should not exceed 3 mA.

32

Auto-reset time (disablement time) of AL at verification (set by a user)

≥5 s

Time of expectation for repeated  triggering after AL resetting, the panel goes to the “Fire” mode on detecting it

60±1 s

Specifications of connectable bells, sounders and beacons

12 (±2) V,    500 mA

Max current load of 4-wire detector outputs

200 mA

Max current load of “Fire”, “Alarm”, “Fault”

40 mA

Meantime-between-failures

30000 hours

Average lifetime

10 years min

Dimensions

200x300x80 mm

Weight (battery excluding)

2,5 kg

 

Specification:

Place of OriginUkraine
Brand NameARTON
Model NumberARTON-02F
UsageFire
Number of zones2
TypeConventional
Average lifetime10 years min
Dimensions200x300x80 mm
Weight2,5 kg
Minimum Order Quantity300 Piece/Pieces
PortOdessa
Packaging DetailsPacked in Carton.
Delivery Time2-4 weeks
Payment TermsL/C,T/T,PayPal
Supply Ability100000 Piece/Pieces per Month

 

 

 