Product Details

Hot and chilled water Fan Coil Units with filter and air return box

Type Other, Air Conditioner Parts, Fan Coil Unit
Application Commercial
Certification CE
Place of Origin Guangdong, China
Brand Name Huali
Model Number HLC~34HC-238HC

Product Features

Hot water Residential Fan Coil Units with filter and air return box

 

Hot and chilled water Fan Coil Units with filter and air return box

 

Horizontal Concealed Fan Coil Unit
  ModelHLC~34HC51HC68HC85HC102HC136HC170HC204HC238HC
Air flow
(m3/h)
 High speed34051068085010201360170020402380
 Medium speed2553835106387651020127515301785
 Low speed17025534042551068085010201190

Cooling capacity
 HighW22473146414650565955775896571160113965
BTU76691073714150172562032426478329593959447663
 MediumW1620244032904120485065508190973011580
BTU5529832811229140621655322355279523320839523
 LowW131020102650332039005300661078609350
BTU447168609044113311331118089225602682631912

Heating capacity
 HighW3251469761897747949111997147321816222137
BTU110961603121123264413239340946502806198775554
 MediumW235035204530604068509260117401414016360
BTU80211201415461206152337931604400694826055837
 LowW1620247031304170474065008180971011290
BTU5529843010683142321617822185279183314038533
Surplus pressure
of outlet (Pa)
 Normal 0 or 12
 High static pressure 30 or 50
 Cooling water temperature7-12°C
Hot water temperature40-60°C
 Power supplyAC220V/50Hz
Heat Exchanger Type 2.2mm copper pipes covered into aluminum fins, fin pitch 2.2mm
Water supply kg/h3244826558149361278160219152178
 Water resistance kPa303030304040404050
 Working pressure1.6MPa

Low static pressure FCU
Input power w3752627696134152189228

Motor power w
101620253020×225×230×240×2
High static
pressure FCU

Static pressrue
30Pa

Input power w
44597287108156174212253

Motor power w
122025304025×230×240×250×2
Static pressure
50Pa

Input power w
496684100118174210250300

Motor power w
162530405030×240×250×260×2
 Fan motor quantity122223444

Noise
dB(A)
 Low static pressure≤37≤39≤41≤43≤45≤46≤48≤50≤52
 High static pressure 30Pa≤40≤42≤44≤46≤47≤48≤50≤52≤54
 High static pressure 50Pa≤42≤44≤46≤47≤49≤50≤52≤54≤56
 Pipe Inlet/outlet water pipe3/4 "internal thread
Condensation water pipe3/4"  external thread
 
Dimension
L mm780880980108011801480168017801880
W mm500500500500500500500500500
H mm260260260260260260260260260
20GP container loading quantity325290260236216172152143135
 40GP container loading quantity666591531482441351309292277
 Main materials         
 Aluminium thickness:0.014mm,  Copper tube thickless:0.35mm,  Galvanized sheet: 1mm,  Packing:  Carton  
           

 

 

 Note:

 

1. Cooling: Indoors DB 27°C,WB 19.5°C; Chilled water inlet/outlet temp. 12°C/7°C.           
2. Heating: Indoors DB WB 21°C, heating water inlet&outlet temperature  60°C/50°C;           
3.The noise level based on: background noise 11.5Db(A) semi-anechoic room.           
4. Water resitance refers to that of rated water flow volume; 
5. Input power refers to that of High speed air flow;       
6. Above parameters are for your reference to model choice of FCU with cooling and heating; Heating energy of one row is 40% of three rows';   Low static pressure air flow  volume loss: 10%, high static pressure air flow volume loss: 20%.     

 

Hot and chilled water Fan Coil Units with filter and air return box

 

 

Hot and chilled water Fan Coil Units with filter and air return boxHot and chilled water Fan Coil Units with filter and air return boxHot and chilled water Fan Coil Units with filter and air return boxHot and chilled water Fan Coil Units with filter and air return box

 

 

Hot and chilled water Fan Coil Units with filter and air return box

Hot and chilled water Fan Coil Units with filter and air return box

 

You May Like

Find Similar Products By Category

You May Like

View More
Chat Now Contact Now